V. sun protection with shading control and variable curtain height and fixed slat position:
The shading control of the weather station is used. The blinds connected to the switching/shutter
actuator are slatted blinds. When the basic brightness for shading operations is exceeded, the weather
station transmits a 1-bit telegram of value "1" via the "Shading facade [shading control facades 1-4]" to
the bus. The switching/shutter actuator activates the shading function and adjusts the corresponding
fixed sun protection position for the slat angle.
The individual facade control of the weather station transmits additionally the blind height to be adjusted
via the 1-byte object "Shading facade curtain height threshold/position [individual control facade ...]" to
the bus. The blind height required for shading will thus be adjusted in the switching/shutter actuator.
When the brightness drops below the basic brightness for shading operations (with hysteresis, if
programmed), the weather station transmits a "0" telegram via the "Shading facade [shading control
facade 1-4]" to the bus . This deactivates the shading function in the switching/shutter actuator and the
corresponding reaction at the end of sunshine /shading will be executed.
Ideally, the telegram "Shading facade curtain height threshold/position [individual control facade ...]" = 0
% is suppressed in the weather station by means of a parameter. The extra blind positioning movement
might otherwise adversely affect the behaviour of the output at the end of shading (possibly brief
bucking).
The communication objects must be linked as shown in Fig. 39.
Required parameterization of the switching/shutter actuator (parameters not listed are optional):
- polarity object "Sunshine / shading facade" = "1" sunshine,
- reaction at the beginning of sunshine / shading = variable blind position, fixed slat position,
- fixed blind position setting.
Weather station
Shutter actuator
sunsh./shading
blind position
(1 byte)
sunshine/shading facade (1 bit)
shading facade…height of curtain
...[individual contral facades 1-4]
(1 byte)
shading facade …
[shading control facades 1-4]
(1 bit)
Fig. 39: Programming of the communication objects for application example V