Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 152 / 174
Offset with fixed and
variable slat position
no offset
offset as
parameterized
offset as parameterized
and via object
For 'manual' readjustment of the slat angle
during a shading or sun position tracking
operation, a slat offset can be preset. The offset
corrects the preset slat angle in positive or in
negative direction. The lighting conditions in a
room can thus be individually adapted by
persons present in the room.
The offset correction is deactivated.
The slat offset is statically preset by means of a
fixed parameter value.
The slat offset is preset by a fixed parameter
value and can be dynamically adapted via a
separate communication object.
This parameter is only visible, if the slat is to
approach a fixed or a variable position at the
beginning of shading.
This parameter is visible only in the 'Blind'
mode of operation.
Offset slat position
(-100..100 %)
-100…
0...100
This parameter is used for setting the slat
offset. The value specified in this parameter is
added at the beginning of shading to the current
slat angle.
Even with offset correction, the 0...100% slat
position limits cannot be overstepped.
It should be noted that the parameterized
offset value can be overwritten by the object
after reception of a dynamical value. -
This parameter is only visible, if the
parameter "Offset with fixed and variable slat
position" is set to "Offset as parameterized"
or to "Offset as parameterized and via
object".
This parameter is visible only in the 'Blind'
mode of operation.