Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 26 / 174
4.2.3
Object table
Number of communication objects:
4/8gang: 74 (max. object number 109 – gaps in between)
8/16gang: 138 (max. object number 213 – gaps in between)
Number of addresses (max):
254
Number of assignments (max):
255
Dynamic table management:
no
Maximum table length:
255
Channel-independent objects:
Function:
Manual control
Object
Function
Name
Type
DP type
Flag
0
Disabling
Manual control
1 bit
1.003
C, W, -, (R)
1
Description:
1-bit object for disabling the keys for manual control on the device. The polarity can be
parameterized.
Function:
Manual control
Object
Function
Name
Type
DP type
Flag
1
Status
Manual control
1 bit
1.002
C, -, T, (R)
1
Description:
1-bit object for manual control status transmission The object is "0", when manual control
is deactivated (bus control). The object is "1", when manual control is being activated.
The user can parameterize whether the temporary or the permanent manual control will
be indicated as status information or not.
Function:
Shutter central function (in shutter mode)
Object
Function
Name
Type
DP type
Flag
2
Central travel control
All shutter outputs
1 bit
1.008
C, W, – (R)
1
Description:
1-bit object for central actuation (long-time travel) of assigned shutter outputs. The
polarity can be parameterized.
1
Each communication object can be read out. For reading, the R-flag must be set.