Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 124 / 174
Minutes (1...59)
1…
2...59
Sets the monitoring time minutes.
Presetting: 2 minutes
The cycle time of the transmitter should be
less than half the parameterized monitoring
time of the actuator.
The times can only be set, if rain alarm
monitoring is activated.
Use frost alarm monitoring
function ?
yes
no
If the rain alarm enabled under "Shutter outputs
safety" is to be monitored cyclically for incoming
telegrams to the safety object, the monitoring
function must be enabled here (setting: "yes").
In the opposite case (setting: "no"), the object is
not monitored cyclically.
As soon as the monitoring function is
activated, telegrams must be transmitted
cyclically to the enabled frost alarm object.
The parameter is only visible, if the frost
alarm has been enabled under "Shutter
outputs safety".
Frost alarm monitoring time
Hours (0...23)
0...23
This parameter is used for programming the
frost alarm monitoring time.
Sets the monitoring time hours.
Minutes (1...59)
1…
2...59
Sets the monitoring time minutes.
Presetting: 2 minutes
The cycle time of the transmitter should be
less than half the parameterized monitoring
time of the actuator.
The times can only be set, if frost alarm
monitoring is activated.