Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 128 / 174
Description:
Values:
Remarks:
Ax – General (x = number of output 1/2 … max. 15/16. / All outputs can be parameterized
independently / Only visible in shutter mode!)
Mode of operation
(to be adjusted first!)
blind
shutter / awning
venting louver
The shutter actuator can be used to control
different drive systems. This parameter defines
which type of drive or which type of curtain is
connected to the output.
The ETS adapts all of the following
parameters (designations, visible/non visible,
etc.) dynamically to the respective mode of
operation parameter. For this reason, the
"Mode of operation" parameter should be
adjusted before all other parameters of an
output.
Behaviour after ETS
programming
raising / opening the louver
lowering / closing the
louver
stop
The actuator permits setting the preferred relay
contact position after ETS programming
separately for each output.
After programming with the ETS, the actuator
raises the curtain or opens the venting louver.
After programming with the ETS, the actuator
lowers the curtain or closes the venting louver.
After programming with the ETS, the actuator
switches the relays of the output to the "stop"
position. A travel movement in progress, if any,
will be interrupted.
The parameterized behaviour will be
executed after every application or parameter
download by the ETS. A simple download of
the physical address alone or partial
programming of only the group addresses
has the effect that this parameter is
disregarded and that the parameterized
"Behaviour after bus/mains voltage return"
will be executed instead.