Description:
Values:
Remarks:
Ax – Forced position (x = number of output 1/2 … max. 15/16. / All outputs can be parameterized
independently / Only visible in shutter mode and if parameter "Forced-position function ?" under "Ax
– Enabled functions" is set to "enabled"! / Only in ETS3.0d and onwards!)
Behaviour at the end of the
forced-position function
tracking the position
no change
The behaviour of the output at the beginning of
a forced-position function is directly determined
by the forced-position telegram. The behaviour
of the output at the end of the forced-position
function can be parameterized.
At the end of the forced-position state, the
output will be set to the position last existing
before the forced-position function or to the one
tracked internally while the forced-position
function was active.
At the end of forced-position state, the position
last adjusted will not be changed. Thereafter,
the output is again enabled.
Behaviour after bus voltage
return
no forced position active
forced position on, raising /
opening the louver
forced position on,
lowering / closing the
louver
state of forced position
before bus/mains voltage
failure
The communication object of the forced position
function can be initialized after bus voltage
return.
After bus voltage return, the forced position
function is deactivated.
The forced-position function is activated after
bus voltage return and the curtain raised or the
venting louver opened.
The forced-position function is activated after
bus voltage return and the curtain lowered or
the venting louver closed.
After bus voltage return, the forced-position
state last selected and internally stored before
bus or mains voltage failure will be tracked. An
ETS programming operation deletes the stored
state (reaction in that case same as with "no
forced position active").
This parameter is evaluated even after an
ETS download of the application or of
parameters.
The forced-position parameters are only
visible, if the parameter "Forced-position
function" under "Ax - Enabled functions" is
set to "enabled".