4.2.5
Parameters
Description:
Values:
Remarks:
General
Delay after bus voltage
return
Minutes (0…59)
0...59
To reduce telegram traffic on the bus line after
bus voltage activation (bus reset), after
connection of the device to the bus line or after
programming with the ETS, it is possible to
delay all active feedbacks of the actuator. The
parameter specifies in this case a delay valid for
all devices. Feedback telegrams for initialization
will therefore be transmitted to the bus only after
the parametrized time has elapsed.
Setting the minutes of the delay time.
Seconds (0...59)
0...
17…59
Setting the delay time seconds.
Central function for outputs
in
switching mode ?
yes
no
Setting "yes" enables the central function and
thus the "Central switching" object. - Individual
switching outputs can be assigned to the central
function only if the function is enabled
Central object polarity
0 = switching off;
1 = switching on
0 = switching on;
1 = switching off
The parameter sets the polarity of the central
object.
Central function for outputs
in
shutter mode ?
yes
no
Setting "yes" enables the central function and
thus the "Central travel control" object.
Individual shutter outputs can be assigned to
the central function only if the function is
enabled.
Central object polarity
0 = UP; 1 = DOWN
0 = DOWN; 1 = UP
This parameter defines the polarity of the
central object.