Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 173 / 174
Behaviour after bus voltage
return
no forced-control
position
activate forced-control
position, ON
deactivate forced-control
position, OFF
state of forced-control as
before bus voltage failure
The communication object of the forced-control
position function can be initialized after bus
voltage return. The switching state of the output
can be influenced when the forced-control
position function is activated.
No forced-control position activated after bus
voltage return.
Forced-control position activated. Output re-
enabled.
Forced-control position activated. The output
will be switched off by forced control.
The output is set to the forced control state
which was stored in a non-volatile memory at
the time of bus voltage failure. After
programming of the application or of the
parameters with the ETS, the value is internally
set to "not active".
After programming of the application or of the
parameters with the ETS, the forced-control
position is always cancelled.
This parameter is only visible, if the
parameter "Selection of supplementary
function is set to "forced-control position".
Logic operation function ?
yes
no
This parameter can be used to enable the logic
operation function (setting "yes"). - After
enabling, the logic operation object and the
parameters of the function are visible.
The parameter is fixed to "no", when the
staircase lighting timer or the cyclical
monitoring functions are enabled.
Type of logic operation
OR
AND
AND with feedback
This parameter defines the type of the logic
operation.
"AND with feedback:"
With a logic object = "0", the output is always
"0" (logic AND). In this case, the feedback
signal from the output to the "switching" input
will directly reset this input when it is being
set. Only if the logic operation object = "1",
can the output adopt the logic state "1" after a
new "1" has been received on the "Switching"
input.
This parameter is only visible, if the
parameter "Logic operation function ? is set
to "yes".