FUNCTIONS
61
COOLING CLIMATIC CURVES
0
2
4
6
8
10
12
14
16
18
20
15
20
25
30
35
40
45
K1
K2
Setpoint dell'acqua (°
C)
OAT (°C)
— If the OAT is valid (not transmitted by the inverter, value out
of range, etc.), the water setpoint is equal to the current min-
imum water temperature.
— If the OAT is above the maximum current OAT threshold, the
water setpoint is equal to the maximum current water tem-
perature.
The climatic curve corresponds to the water setpoint for the Home
mode. To define the other occupancy modes, it is necessary to
configure the Night cooling offset [P408] and the Away cooling off
-
set[P409]:
COOLING CLIMATIC CURVES RELATED TO WORKING MODE HOME
0
5
10
15
20
25
10
15
20
25
30
35
40
45
50
Home
Sleep
Away
P409
P408
WSP (°
C)
OAT (°C)
RISCALDAMENTO:
If the climatic heating curve[P581] รร con
-
figurata da "0" a "12", the water set point will be calculated on the
basis of the selected heating climatic curve.
Twelve predefined heating climatic curves are available:
Climatic curve
OAT min.
OAT max.
Temp. water min.
Temp. water max.
K1
-7°C
20°C
20°C
38°C
K2
-5°C
20°C
20°C
33°C
K3
-9°C
20°C
20°C
45°C
K4
-8°C
20°C
40°C
50°C
K5
-5°C
20°C
40°C
55°C
K6
0°C
20°C
40°C
60°C
K7
-20°C
20°C
22°C
42°C
K8
-20°C
20°C
23°C
55°C
K9
-12,7°C
20°C
24°C
60°C
K10
-5,9°C
20°C
25°C
60°C
K11
-1,5°C
20°C
26°C
60°C
K12
3,5°C
20°C
27°C
60°C