![Beretta 20161618 Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/beretta/20161618/20161618_installer-manual_2736692053.webp)
INSTALLATION
53
HYDRONIC UNIT B
53
Par
.
Jbus
Mnemonic
Description
Field
Default
Unit
Control panel
CCN
Table
573
ADD_PUMP_LOGIC
Additional pump logic
0÷4
0 = No additional pump
1 =
Always on
2 = In accordance with the ambient temperature (remote WUI)
3 =
Always on, of
f when DHW mode is activated
4 = In accordance with room temperature (remote WUI), but of
f when in
DHW mode
0
-
RW
PMP_CONF
581
0870H
HEA
T_CUR
V
Heating climatic curve selection
-1 = No curve, fixed setpoint
0 = Custom curvePar
.582/Par
.585
1 = Heating curve #1 2 = Heating curve #2 3 = Heating curve #3 4 = Heating curve #4
…
12 = Heating curve #12
-1
-
RW
RW/No Force
CLIMCUR
V
582
0876H
CUST_HEA
T_MIN_OA
T
Minimum OA
T heating
-30.0÷10.0
-7.0
1/10°C
RW
RW/No Force
CLIMCUR
V
583
0877H
CUST_HEA
T_MAX_
OAT
Maximum OA
T heating
10.0÷30.0
20.0
1/10°C
RW
RW/No Force
CLIMCUR
V
584
1902H
CUST_MIN_TEMP_
HEA
T
Minimum heating water setpoint
20.0÷40.0
20.0
1/10°C
RW
RW/No Force
CLIMCUR
V
585
1904H
CUST_MAX_TEMP_
HEA
T
Maximum heating water setpoint
30.0÷60.0
38.0
1/10°C
RW
RW/No Force
CLIMCUR
V
586
0875H
COOL_CUR
V
Cooling climatic curve selection
-1÷2
-1 = No curve, fixed setpoint
0 =Custom curve Par
.587/Par
.590
1 = Cooling curve #1 2 = Cooling curve #2
-1
-
RW
RW/No Force
CLIMCUR
V
587
087BH
CUST_COOL_MIN_
OAT
Minimum cooling OA
T
0.0÷30.0
20.0
1/10°C
RW
RW/No Force
CLIMCUR
V
588
087AH
CUST_COOL_MAX_
OAT
Maximum cooling OA
T
24.0÷46.0
35.0
1/10°C
RW
RW/No Force
CLIMCUR
V
589
1903H
CUST_MIN_TEMP_
COOL
Minimum cooling water setpoint
5.0÷20.0
10.0
1/10°C
RW
RW/No Force
CLIMCUR
V
590
1905H
CUST_MAX_TEMP_
COOL
Maximum cooling water setpoint
5.0÷20.0
18.0
1/10°C
RW
RW/No Force
CLIMCUR
V
595
DR
YING_ST
AR
T_
SETPOIN
Drying start setpoint
20.0÷40.0
20.0
1/10°C
RW
DR
YING
596
DR
YING_W
ARM_UP_
DA
YS
Heating drying days
0÷99
3
-
RW
DR
YING
597
DR
YING_RAMP_UP_
DA
YS
Days ramp upward drying
0÷99
4
-
RW
DR
YING
598
DR
YING_HOLD_UP_
DA
YS
Drying ramp maintenance days
0÷99
4
-
RW
DR
YING
599
DR
YING_HOURS