INSTALLATION
55
HYDRONIC UNIT B
55
Par
.
Jbus
Mnemonic
Description
Field
Default
Unit
Control panel
CCN
Table
653
050DH
PIC_TYPE
PIC type
“30R
V”
-
RO
RO/No Force
30RBVRQV
654
SOFT_VERSION_NB
Software number
0
-
RO
30RBVRQV
661
HOUR
Time
0÷23
0
-
RW
Time
662
MINUTE
Minute of the hour
0÷59
0
-
RW
Time
663
DA
Y_OF_WEEK
Day of the week
1÷7
1 = Monday 2 = T
uesday
3 = W
ednesday
4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday
0
-
RW
Time
664
HOLIDA
Y_FLAGS
Flag vacancy
0÷
1111111
0
Bitmap:b7 : Monday
b6
: T
uesday
b5 : W
ednesday
b4
: Thursday
b3 : Friday b2 : Saturday
b1 : Sunday b0 : unused
0
-
RW
Time
665
DA
Y_OF_MONTH
Day of the month
1÷31
0
-
RW
Time
666
MONTH
Month
1÷12
1 = January
…
12 = December
0
-
RW
Time
667
YEAR
Year
0÷99
0
-
RW
Time
701
DHW_TYPE
Type of domestic hot water
0÷3
0 = No DHW
1 = NO 2-point diverter valve 2 = 2-point NC diverter valve 3 = Dedicated DHW circulator
0
-
RW
DHW_CONF
702
DWH_V
AL
VE_
RUNTIME
DHW 3-way valve operating time
0÷240
30
s
RW
DHW_CONF
703
DHW_PRIORITY
Priority DHWS
0/1
0 = Automatico
1 = DHW
0
-
RW
DHW_CONF
704
SHC_MIN_RUNTIME
Minimum operating time SHC
0÷720
20
min
RW
DHW_CONF
707
DHW_MAX_RUNTIME
Maximum DHW operating time
-1÷720
240
min
RW
DHW_CONF
708
DHW_EXCEPTION_
TIME
DHW exception time
1÷24
2
Time
RW
DHW_CONF
710
DHW_VSP_SPEED
Maximum pump speed in DHW mode
19÷100
100
%
RW
DHW_CONF
Содержание 20161618