FUNCTIONS
60
3.5 Functions
3.5.1 Acronyms
IAT
Indoor Air Temperature
BPHE
Plate heat exchanger
CHWS
(Chiller Water System), system water circuito
DHW
Domestic Hot Water
EHS
Electric heater stage
EWT
Entering Water Temperature
FCU
(Fan Coil Unit), Fan Coil Unit
LWT
Leaving Water Temperature
NHC
New Hydronic Control
OAT
Outdoor Air Temperature
PMV
Pulse Modulating Valve
SHC
Space Heating/Cooling Control
TR
Refrigerant Temperature
UFC
Underfloor Cooling
UFH
Underfloor Heating
CHWSTEMP
DHW: (DHW) Domestic hot water
WUI
User Interface (Wall-mounted User Interface)
3.5.2 Setpoint
Depending on the unit configuration, the system control can be
based on the water or air setpoint control.
To achieve greater comfort, you can adjust the room temperature
setpoint (remote user interface) or the water temperature setpoint
(local user interface) according to your needs. Please note that the
temperature value can only be adjusted within the range defined
for each occupation mode.
Possible configurations
Setpoint
WUI local
WUI remote
Room air probe
Water
Air
The calculation of the water setpoint can be based on:
Predefined climatic curves
based on the OAT: climatic curves
already defined in the control logic.
Fixed water setpoint:
by entering a fixed value for each occupa
-
tion mode.
Custom climatic curve
based on the OAT: defines climatic curves
customized according to the application.
Offset on climatic curves (predefined and user-defined)
Default climatic curves
RAFFREDDAMENTO:
If the climatic cooling curve[P586] รร im
-
postata su "0", "1" o "2", the water set point will be calculated based
on the selected cooling climatic curve.
Two predefined cooling climatic curves are available:
Climatic curve
OAT min.
OAT max.
Temp. water min.
Temp. water max.
K1
20°C
40°C
5°C
10°C
K2
20°C
40°C
10°C
18°C