97
6.4 Setting zone's climatic curve
parameters (accessible only with
installer password)
Menu
→
“Settings”
→
“Zone Clim. Curve”
- press the
►
key so that the number is highlighted on the right
of the word "Zone";
- use the
▲
and
▼
keys to change the zone number;
- press the
●
key.
The following is displayed:
“
Outdoor reset
”
“
Setp.
[°C
]
”
“
Des. Supply T.
”
82.0
“
°C
”
“
Bas. Supply T.
”
40.0
“
°C
”
“
WW Shutdown
”
21.0
“
°C
”
“
Bas. Outd. T.
”
21.0
“
°C
”
“
T Outside [°C]
”
“
Des. Outd. T.
”
-4.0
“
°C
”
90
0
-15
35
The “Comp. T. @ T.ext. Max” parameter, if other than 0, transforms
the climatic curve from linear to quadratic allowing you to best adapt
the variation of the setpoint to the variation of the outdoor temperature.
The resulting quadratic climatic curve will have three parameters:
- Heat. Set. Max
- Baseline Outdoor Temp.
- Text. Min
of the basic linear climatic curve and a value of the Heat. Set. Min.
diminished by the value of the parameter “Comp. T. @ T.ext. Max”, as
can be seen in the example in the figure.
Delivery Temp.
(°C)
Outdoor Temp. (°C)
Comp. T. @ T.ext. Max
Min Outdoor Temp.
Baseline Outdoor Temp.
Shutdown Temp.
Max. Heating Set.
Min. Heating Set.
6.5 Programming the zone
By default the schedule timer is disabled.
In fact, to start a request from the zone just close the contact of the
zone request. In this case the thermal module (or the cascade of ther-
mal modules) will start with a setpoint equal to the value calculated on
the zone climatic curve increased by the “Zone Extra Setpoint” value
and the mix valve will modulate to maintain the delivery temperature
of the zone at the calculated setpoint.
To activate zone programming:
Menu
→
“Settings”
→
“Clock Settings”
“
Settings
”
“
Clock Settings
”
“
Appliance Configuration
”
“
External Zone Settings
”
“
Ext. Zone Climatic Curve
”
p
Confirming with
●
the following screen is displayed:
“
Clock Settings
”
“
CH Clock
”
“
Disabled
”
“
DHW Clock
”
“
Disabled
”
“
CH Ext. Zones Clock
”
“
Disabled
”
- with the
▲
/
▼
keys select “CH Zones clock”
- with the
►
key move to “Disabled”, change it to “Enabled” with
the
▲
/
▼
keys
- confirm with the
●
key
Go to:
Menu
→
“Clock program”
Confirming with the
●
key:
“
Clock Program
”
Program CH Zone Ext.
1
“
Program Group
”
1
“
Holiday Settings
”
“
Season Settings
“
At this point select the number of the zone to be programmed and
confirm with the
●
key.
“
External Zone
”
1
“
Program Comfort Period
”
1
“
Comfort Setpoint
”
20.0
“
°C
”
“
ECO Setpoint
”
5.0
“
°C
”
“
Out of interval setpoint
”
“
Anti Fr
”