2.14.2 Parameters' list
Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Access type
U
End user
I
Installer
O
Manufacturer
Menu Par.
No.
Display
visualis-
ation
Description
Range
Default
setting
UM
Access
type
Category
M1
1
CH mode
Defines the thermal module's various
heating operation modes.
0…5
0
I
Heating
M1
3
CH set-
point
Defines the desired delivery temperature
in heating mode (Par. 1) = 0.
Par. 23…Par. 24
70
°C
U
Heating
M1
109
Calc.
set-point
off-set
Establishes the set-point offset value
calculated in climatic mode (Par. 1= 1).
Offsets the climatic curve in presence of
mild outdoor temperatures.
Off, -10…10
0
I
Heating
M1
110 CH Min.
Set-point
The minimum delivery temperature at
which the system operates in both heat-
ing and DHW mode.
20…50
30
°C
I
Heating
M1
111 CH Max.
Set-point
The maximum delivery temperature at
which the system operates in both heat-
ing and DHW mode.
50…90
80
°C
I
Heating
M1
5
Boiler
Pump
Overrun
Sets the overrun time in seconds of the
boiler's circulator during stand-alone op-
eration; cascaded operation determines
the module's overrun after switch-off due
to temperature control.
0…900
60
Sec.
I
Heating
M1
6
Flue
Temp.
Limit
Sets the activation temperature when
the maximum flue gas temperature is
exceeded. When the flue gas tempera-
ture is higher than a set value, the module
switches off and an error message is
generated. When the flue gas tempera-
ture is in the interval between (Par. 6) -5°C
and Par. 6, the module reduces its power
in a linear way until it reaches minimum
power when the temperature measured is
equal to Par. 6.
10…120
100
°C
O
General
M1
7
CH Hys-
teresis
Sets the value in degrees beyond the set-
point at which the burner switches off for
thermoregulation.
0…20
5
°C
I
Heating
M1
112
CH
Hysteresis
Down
Sets the value in degrees below the
set-point at which the burner switches on
again for thermoregulation.
0…20
5
°C
I
Heating
M1
9
Anti-cycle
Period
Sets the stand-by time before the appli-
ance is switched on again after it switches
off due to thermoregulation, independent-
ly from the delivery temperature dropping
below the value indicated in Par. 10.
Parameter valid only in stand-alone mode.
10…900
120
Sec.
I
Heating
M1
10
Anti-cycle
Temp.
Diff.
Sets the value in degrees below which the
burner switches on again notwithstanding
from the time spent at Par. 9.
0…20
16
°C
I
Heating
M1
12
Hx diff.
Minimum
Sets the value of the temperature differ-
ence (Delta T) between the module's
delivery and return temperature. For a
Delta T value ranging between Par. 12
and (Par. 12) +8°C, the module reduces
its power in a linear fashion until it reaches
the minimum power. The minimum
power is maintained until reaching (Par.
12) +8°C+5°C, after which the module
switches off for a period of time equal to
the value attributed to Par. 13; at the end
of this time interval, the module switches
on again.
10…60
40
°C
O
General
M1
13
Hx Diff.
Max. Wait
Time
Defines the restart time after reaching the
Delta T limit between delivery and return.
10…250
30
Sec.
O
General
M1
14 Max. Pow-
er CH
Sets the heating's % max. power.
50…100
100
%
I
Heating