53
Menu Par.
No.
Display
visualis-
ation
Description
Range
Default
setting
UM
Access
type
Category
M1
121 Prog Input
6.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = T_Flue sensor
2 = Flue switch
3 = APS switch
0,1,2,3
Defined by
Par. 97
I
General
M1
122 Prog Input
7.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = T_Flue_2 sensor
2 = T_ Bl. Flue
3 T_System sensor
4 = Blocked Flue switch 5 Cascade
Sensor
0,1,2,3,4,5
Defined by
Par. 97
I
General
M1
123 Prog Input
8.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = T_DCW sensor
2 = Water pressure switch
0,1,2
Defined by
Par. 97
I
General
M1
124
Prog.
Input RT.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = Enabled
0,1
Defined by
Par. 97
I
General
M1
125
Prog.
Output 1.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 = DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
9 = External Igniter
10 = Air Damper
14 = Alarm Burner CC
15 = Status Burner CC
17 = Antilegionella pump
0,1,2,3,4,5,6,7,
8,9,10,14,15,17
Defined by
Par. 97
I
General
M1
126
Prog.
Output 2.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 = DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
9 = External Igniter
10 = Air Damper
14 = Alarm Burner CC
15 = Status Burner CC
17 = Antilegionella pump
0,1,2,3,4,5,6,7,
8,9,10,14,15,17
Defined by
Par. 97
I
General
M1
127
Prog.
Output 3.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = General Pump
10 = Air Damper
11 = External Igniter
12 = Modulating Pump
0,1,10,11,12
Defined by
Par. 97
I
General
M1
128
Prog.
Output 4.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 =DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
0,1,2,3,
4,5,6,7,8
Defined by
Par. 97
I
General
M1
129
Flow
sensor
Defines the type of flow sensor used.
Bitron, Huba: DN8,
DN10, DN15,
DN15, DN20, DN25
Huba DN25
I
General
M1
133
Mod.
Pump dT
Defines the delta T set for the operation of
the modulating circulator.
5…40
15
°C
I
General