10
Description
Power Max BOX
U.M.
130-2 P
160-2 P
200-2 P
260-2 P
300-2 P
POWERS AND EFFICIENCY
Nominal rated heat input (PCI)
114
136
180
223,2
262
kW
Nominal rated heat input (PCS)
126
152
200
248
292
kW
Maximum rated heat output (80°-60°C)
G20
111,4
134
176,6
219,6
258
kW
Maximum rated heat output (60-40°C)
G20
119,2
142,8
187,6
232,4
274,6
kW
Maximum rated heat output (50-30°C)
G20
123,8
147,8
194,8
242,2
284,2
kW
Minimum rated heat input (PCI)
G20
13,7
13,7
19,4
22,4
26,3
kW
Minimum rated heat input (PCS)
G20
15
15
21,6
24,9
29
kW
Minimum thermal output 80/60°C
G20
13,5
13,5
19,2
22,1
26
kW
Minimum thermal output 50/30°C
G20
14,9
14,9
21,1
24,5
28,9
kW
Useful efficiency at nominal heat output 80-60°C (PCI)
97,72
98,53
98,11
98,40
98,47
%
Useful efficiency at minimum heat output 80-60°C (PCI)
98,9
98,9
98,8
99,2
99,1
%
Useful efficiency at nominal heat output 50/30°C (PCI)
108,6
108,1
108,3
108,6
108,3
%
Useful efficiency at minimum heat output 50/30°C (PCI)
109,3
109,3
109,2
110
110
%
Useful efficiency 30% - 50/30°C PCS (PCI)
98,94
(109,36)
97,81
(109,31)
98,00
(108,89)
98,39
(108,93)
98,17
(109,41)
%
Combustion efficiency
99,0
99,0
99,0
99,3
99,3
%
Chimney losses with burner off
0,1
0,1
0,1
0,1
0,1
%
Chimney losses with burner on P. max. 80-60°C
2,3
2,3
2,5
2,5
2,6
%
Chimney losses with burner on at 30% Pn 50-30°C
0,5
0,5
0,6
0,5
0,6
%
Chimney losses with burner on P. min. 80-60°C
0,12
0,11
0,22
0,1
0,1
%
Losses through the casing with average T 70°C and burner on
0,5
0,5
0,5
0,5
0,5
%
Losses through the casing with average T 70°C and burner off
0,5
0,5
0,5
0,5
0,5
%
Flue gas temperature at max power and min power 80-60°C
71 - 61
72 - 61
76 - 62
75 - 61
77 - 61
°C
Flue gas temperature at max power and min power 50-30°C
45 - 33
46 - 33
47 - 35
45 - 33
48 - 35
°C
Air index
λ
at max power
G20
1,27
1,27
1,27
1,27
1,27
no.
G31
1,29
1,29
1,29
1,29
1,29
no.
Air index
λ
at min power
G20
1,27
1,27
1,27
1,27
1,27
no.
G31
1,29
1,29
1,29
1,29
1,29
no.
Max Flue flow at max-min power
G20
53 - 6
64 - 6
84 - 9
104 - 10 122 - 12 g/s
G31
51 - 6
62- 6
82 - 9
101 - 10 119 - 12 g/s
Flue Residual prevalence at min power
35
35
32
30
28
Pa
Flue gas residual head with max power
510
630
560
500
353
Pa
Maximum rated heat input (LCV)
G25
106
130
170
214
254
kW
Minimum rated heat input (LCV)
G25
13
13
18,1
21,4
24,5
kW
(*)
Configurations possible only with the installation of the dedicated accessories (available separately).