Stabilization Time (Key/LED 1)
The LED will go On to indicate that the system is ready
to start the programming procedure.
Use the
Increase Time
option (Key
8
) or
Decrease
Time
option (Key
0
), respectively, to increase or decre-
ase the setting.
The setting is achieved by adding together the values
indicated by the LEDs in column
B
(e.g. if the
8 sec
and
2 sec
LEDs are On, the setting will be 10 seconds).
n
Reset Time (Key/LED 2)
The LED will go On to indicate that the system is ready
to start the programming procedure. This setting is
achieved and formatted as per the Stabilization Time.
n
Silenceable Outs (Key/LED 4)
The LED will go On to indicate that the system is ready to
start the programming procedure. Using key
3
(
ALARM
)
assign the Silenceable attribute to the ALARM output:
– if the
ALARM
LED is On, the ALARM Output is Silen-
ceable;
– if the
ALARM
LED is Off, the ALARM Output is not Si-
lenceable.
n
Configuration 1 (Key/LED 5)
The LED will go On to indicate that the system is ready
to start the programming procedure. Using the keys in
columns
E
and
F
, configure the Control panel:
– if the LED is On, the respective Module is included in
the configuration;
– if the LED is Off, the respective Module is NOT inclu-
ded in the configuration.
During this phase, the keys and LEDs in columns
E
and
F
will operate in accordance with the options written in
positive type
:
Ø
Exting. 1
= Extinguishment Module nr. 1
Ø
Exting. 2
= Extinguishment Module nr. 2
Ø
Expander 1
= Expander Module nr. 1
Ø
Expander 2
= Expander Module nr. 2
Ø
Power 1
= Power Station nr. 1
Ø
Power 2
= Power Station nr. 2
Ø
Power 3
= Power Station nr. 3
Ø
Power 4
= Power Station nr. 4
n
Configuration 2 (Key/LED 7)
The LED will go On to indicate that the system is ready
to start the programming procedure. Using the keys in
columns
E
and
F
, configure the Control panel:
– if the LED is On, the respective Module is included in
the configuration;
– if the LED is Off, the respective Module is NOT inclu-
ded in the configuration.
During this phase, the keys and LEDs in columns
E
and
F
will operate in accordance with the options written in
negative type
:
Ø
LCD 1
= LCD Module nr. 1
Ø
LCD 2
= LCD Module nr. 2
Ø
LCD 3
= LCD Module nr. 3
Ø
LCD 4
= LCD Module nr. 4
Ø
Rep. 1
= Repeater panel nr. 1
Ø
Rep. 2
= Repeater panel nr. 2
Ø
Rep. 3
= Repeater panel nr. 3
Ø
Rep. 4
= Repeater panel nr. 4
The “MODULES” Programming Phase
The
MODULES
LED will blink to indicate that the
system is ready to program the parameters of the Extin-
guishment Modules. During this phase, the keys and
LEDs will operate in accordance with the options prece-
ded by
in the panes on the Programming Overlay,
see Figure 34.
The LED (
Exting. 1
or
Exting. 2
) corresponding to the
Extinguishment Module concerned will blink to indicate
that the system is ready to program the respective para-
meters.
Press key
1
(
Extinguish. time
),
2
(
Pre-exting. time
) or
4
(
Activation Zones
) to select the parameter you want
to program then refer to the respective paragraph
or
,
press the
Next phase
key
9
to go back to the
ZONE
Programming Phase (see column
A
).
n
Extinguish. time (Key/LED 1)
The LED will go On to indicate that the system is ready
to start the programming procedure.
PROGRAMMING FROM THE PANEL
49
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
Gas detector
N
1 sec
5 sec
C
N
2 sec
Test on NACs
NAC1 Alarm
4 sec
NAC2 Alarm
8 sec
Silen. Out R
ALARM
16 sec
OC output
32 sec
160 sec
Alarm verific.
64 sec
320 sec
128 sec
640 sec
MODULES
VARIOUS
PANEL
OUTPUTS
TIMES
ZONES
-
Refresh time
Pre-alarm
Day mode
Reset time
Zone 1
Zone 1
Fault
Exting. 1
ALARM
LCD 1
Zone 5
Zone 5
Power 1
Rep. 1
Zone 5
Zone 2
Zone 2
Test
Exting. 2
LCD 2
Zone 6
Zone 6
Power 2
Rep. 2
Zone 6
Zone 3
Zone 3
Expander 1
LCD 3
Zone 3
Zone 7
Zone 7
Power 3
Rep. 3
Zone 7
Zone 4
Zone 4
Expander 2
LCD 4
Zone 4
Zone 8
Zone 8
Power 4
Rep. 4
Zone 8
Zone 2/Exting. 2
-
Silenceable outs
Verification time
Reset
Night mode
Activation zones
-
Pre-alarm time
Alarm
User code
Stabilization time
Extinguish. time
-
Silence time
Disablement
Clock
Configuration 1
-
Configuration 2
DL output delay
Double knock
Date
1
2
3
4
5
6
7
8
9
0
Next Option
Decrease time
Next Output
Decrease time
Decrease time
-
Increase time
Mains off delay
Increase time
Increase time
Next phase
C
B
A
E
F
D
Pre-alarm on R
Detect missing
Call-point alarm
NAC2 Pre-alarm
NAC1 Pre-alarm
Zone 1/Exting. 1
Figure 34
The “Modules” Programming Phase
Содержание J408
Страница 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...
Страница 12: ...C N O N C 6 7 8 10 11 26 27 28 29 30 31 9 Figure 2 Maximum configuration of the J424 Control panel...
Страница 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...
Страница 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...
Страница 52: ...44 Conventional Fire Panels J424 J408...
Страница 61: ...QUICK GUIDE 53...
Страница 62: ...54 Conventional Fire Panels J424 J408...
Страница 63: ...QUICK GUIDE 55...