Connecting a Power Supply
+
The power circuits of this Control panel comply
with the EN54-4 standard.
!
In order to comply with the Safety regulations
in force, the Mains must be equipped with a bi-
polar isolating device for protection against
over voltage and short-circuit to Earth (e.g. au-
tomatic isolating switch).
This Control panel is powered from the Mains
(230V/50 Hz) through a Switching power supply, loca-
ted inside the case. The
J408
Control panel provides
housing for two 12 V, 7 Ah maximum batteries, where-
as, the
J424
Control panel provides housing for two
12 V, 17 Ah maximum batteries for power during Mains
failure. The non-volatile memory will hold the program-
med data at all times.
In the event of Mains failure, the:
Ø
GREEN
Mains
LED will turn OFF
Ø
RED
Mains
LED will turn ON
The Control panel will monitor the batteries at all times,
(refer to
Static Test
and
Dynamic Test
).
Static Test
The
Static
Test monitors the battery char-
ge during Mains failure. In the event of
Low battery
sta-
tus (below 22.8 V), the
Battery
LED will turn ON. If this
occurs, the Mains power must be restored before the
batteries empty, otherwise, the system will shutdown.
Low battery restoral (over 24.6 V) will be signalled by
blinking on the
Battery
LED (Memory).
Dynamic Test
The
Dynamic
Test monitors the opera-
ting capacity of the batteries. In the event of a Failed
Test result (batteries do not meet the Test require-
ments), The
Battery
LED will turn ON.
If this occurs, the backup battery must be replaced im-
mediately, otherwise, the system will be unable to fun-
ction in the event of Mains failure (black-out).
Battery trouble restoral will be signalled by blinking on
the
Battery
LED (Memory).
n
Connecting the Mains Supply
Work carefully through the following steps (refer to the
figures on pages 12, 14, 18 and 19).
1.
Locate the backup batteries in the housing
20
.
2.
Using the Jumper (supplied), connect the batteries
in series.
3.
Observing the battery polarity, connect the battery
terminals to the wires
60
.
+
If you are connecting 17 Ah batteries, you must re-
place the wire
60
and jumper connectors.
+
J424:
Use 17 Ah @ 12 V YUASA NP 17-12 FR bat-
teries;
J408:
Use 7Ah @ 12 V YUASA NP7-12 FR batte-
ries; or similar with case flame class UL94-V2 (or
higher).
4.
Connect the
Earth
wire to the [
Q
] terminal on the
terminal board
53
.
5.
Connect the
Neutral
wire to terminal [N], and the
Line
wire to terminal [L] on the terminal board
53
.
+
The Control panel will reset on power up.
34
Conventional Fire Panels
J424/J408
L
Main board
N
Automatic
Isolating
Switch
+
–
12 V battery
Line
Neutral
Earth
230 V
50 Hz
+
–
12 V battery
Power supply
RED wire
BLACK wire
Jumper
Figure 20
Wiring diagram for the power supply
Содержание J408
Страница 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...
Страница 12: ...C N O N C 6 7 8 10 11 26 27 28 29 30 31 9 Figure 2 Maximum configuration of the J424 Control panel...
Страница 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...
Страница 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...
Страница 52: ...44 Conventional Fire Panels J424 J408...
Страница 61: ...QUICK GUIDE 53...
Страница 62: ...54 Conventional Fire Panels J424 J408...
Страница 63: ...QUICK GUIDE 55...