Standby status
Only the green Mains LED (and the
Night Mode
LED, if
the Control panel is operating in Night Mode) will be On
during standby status, the display will show the time
and date and “PANEL WORKING” message:
PANEL WORKING
17:30 13/10/2004
PREALARM (ALERT!)
In the event of a fire, the Control panel will first generate
PREALARM, which will be signalled by:
Ø
the devices set up by the installer;
Ø
the
Pre-al.
LED (On);
Ø
the
Zone Alarm
LEDs (On) of the zones concerned;
Ø
an intermittent audible signal (0.5 second beep follo-
wed by a 0.5 second pause);
Ø
a “PREALARM” message, similar to the following:
PREALARM
Warehouse
The bottom line will show the label (e.g Warehouse) of
the zone that triggered the PREALARM.
During PREALARM status, you can:
Use
Ú
or
Ù
to scroll the zones in PREALARM status.
If you do not strike a key within 20 seconds, the display
will go back to the first zone that triggered the
PREALARM.
Press
Esc
to access the Main menu.
If you do not strike a key within 20 seconds, the display
will show the first zone that triggered the PREALARM.
PREALARM status will last for the pre-set Time (refer
to the following paragraph for details).
+
The Control panel will generate an instant Alarm, if
alarm conditions are detected during
Night Mode
(refer to “Night Mode”) or, if an alarm is triggered
from a Call point — connected to a zone with the
Call point priority
attribute (i.e.
Call point priority
ENABLED).
ALARM
ALARM status will be signalled by:
Ø
the devices set up by the installer;
Ø
the
Alarm
LED (On);
Ø
the
Zone Alarm
LEDs of the zones concerned (On);
Ø
a fast intermittent audible signal (0.2 second beep
followed by a 0.2 second pause);
Ø
a “ALARM” message, similar to the following:
ALARM ON ZONE 01
Warehouse
The top line will show the number of the zone that trig-
gered the ALARM; the bottom line will show the zone la-
bel (e.g Warehouse).
During ALARM status, you can:
Use
Ú
or
Ù
to scroll the zones in ALARM status.
If you do not strike a key within 20 seconds, the display
will go back to the first zone that triggered the ALARM.
Press
Esc
to view the Main menu.
If you do not strike a key within 20 seconds, the display
will go back to first zone that triggered the ALARM.
If zones restore to standby spontaneously, the ALARM
events will be stored in the Memory and signalled on the
respective
Zone Alarm
LEDs until you Reset the Con-
trol panel.
+
The Fire Alarm Outputs will not restore to standby
until you Reset the Control panel — even if Alarm
conditions end beforehand.
FAULT
FAULTS will be signalled by:
Ø
the devices set up by the installer;
Ø
the
Fault
LED (On);
Ø
the respective
Fault
LED (On) — refer to Table 1;
Ø
a slow intermittent audible signal (1 second beep fol-
lowed by a 1 second pause);
Ø
a message on the display, similar to the following (re-
fer to Table 1):
FAULT ON ZONE 01
Warehouse
During FAULT status, you can:
Use
Ú
or
Ù
to scroll the Faults list.
If you do not strike a key within 20 seconds, the display
will go back to the first fault that occurred.
Press
Esc
to view the Main Menu.
If you do not strike a key within 20 seconds, the display
will go back to first FAULT that occurred.
If FAULTconditions clear spontaneously, the respective
events will be stored in the Memory, and will be signal-
led by slow flashing on the respective LEDs.
+
The Control panel will restore to standby when all
the FAULT conditions clear.
2
Conventional Fire Panels
J424/J408
Содержание J408
Страница 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...
Страница 12: ...C N O N C 6 7 8 10 11 26 27 28 29 30 31 9 Figure 2 Maximum configuration of the J424 Control panel...
Страница 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...
Страница 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...
Страница 52: ...44 Conventional Fire Panels J424 J408...
Страница 61: ...QUICK GUIDE 53...
Страница 62: ...54 Conventional Fire Panels J424 J408...
Страница 63: ...QUICK GUIDE 55...