background image

Version:1024151027E

- 1 -

Instruction Manual of JTY-GD-930KE Point-type Photoelectric

Smoke Detector

------ Please read this Manual carefully before installing and using the product.

-----

I. Product overview

JTY-GD-930KE point-type photoelectric smoke detector (Detector hereunder) is a two-wire

switch-type smoke-sensing detector. As a non-polar two-wire connection is adopted in the detector, it is

compatible in conventional switch-type alarm control systems and monitoring
alarm systems. The detector can also be connected with intelligent bus fire
alarm control systems via the interface module. The detector monitors smoke
concentration in the workplace in real time. While monitoring, the red indicator
blinks and the working current is low. When the work site smoke
concentration has exceeded the preset alarm threshold, the alarm detectors
and the red indicator remain on, while the loop current is increased. The
detector’s alarm signal can be locked and is displayed by changes in the loop
current. The alarm can only be reset by the instant power disconnection.

The detector is applicable in places where fire might generate volume smoke, i.e. in industrial and

civil buildings such as in the restaurant, hotel, teaching building, office building, computer room, archives
and stack room.

II. Product features

Designed with an upper cover and a lower cover, it can be installed, debugged and maintained

conveniently.

Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest

144 historical data and realize a curve tracing for the field situation.

It has a temperature, humidity and dust accumulation drift compensation function.

III. Technical parameters

1.

Executive standard: GB4715-2005

2.

Operating voltage: DC24V ±20%

3.

Operating current: During monitoring <50uA.

In alarm mode 1mA~10mA (depends on the loop current limiting resistance).

4.

Working indicator: During monitoring, the red indicator blinks once per 6 seconds.

In sensor failure alarm, the red indicator blinks twice per 6 seconds
In fire alarm mode, the red indicator remains on.

5.

Weight: about 100g

6.

External dimensions: diameter: 100mm, height: 55mm (with the base)

7.

Wiring method: non-polarity two-bus system

8.

Operating environment: Indoor, temperature:

10

℃~

+55

; relative humidity:

95% (40

±

2

, without condensation)

9.

Installation height:

12m

10.

Protection area: about 60m

2

. For details, see related provisions in GB50116-98

Code for

Design of Automatic Fire Alarm System

11.

Matched host machine: conventional switch-type fire alarm control system, or intelligent bus

fire alarm control system via the interface module.

IV. Appearance and dimensions (see Fig.1)

(Unit: mm)

Fig.1

Screw cover

A

Indicator

- 2 -

V. Use and engineering application

1.

Fig.2 is the schematic diagram of the matched mounting base.

DZ

-9

10

K

Fig.2

Definitions of terminals(non-polarity

two-wire system):

1 – L2 Signal terminal

2 – L1 Signal terminal

3 – L1 Signal terminal

4 – No Pin

Notes

Terminal 2 and 3 are connected

directly inside the detector. Connecting

the detector with the controller as Fig.3,

we can find the failures caused by

dismounting the detector.

2.

Wiring method:

a.

Fig.3 is a schematic diagram of the connection between multiple detectors with a

conventional switch-type (current type)alarm control systems.

DZ

-9

10

K

DZ

-9

10

K

DZ

-9

10

K

Fig.3

b.

Fig.4 is a schematic diagram of the connection between multiple detectors with

intelligent two-bus fire alarm control system via the interface module.

Intelligent 

two-bus fire alarm 

control panel

L2

L1

GND

+24V

Input module

TO+

TO-

Terminal load(4.7K)

DZ

-9

10

K

DZ

-9

10

K

DZ

-9

10

K

Fig.4

VI. Installation and debugging

Determine the location, mounting distance and numbers for mounting the detectors in the protection

area according to relevant provisions and regulations of GB50116-98

Code for Design of Automatic Fire

Alarm System

and GB50166-2007

Code for Installation and Acceptance of Fire Alarm System

.

A self-contained complete base is necessary during the installation of a detector. As shown in Fig.5,

the model, the external dimensions, the mounting hole diameter and the mounting hole spacing of the
base are DZ-910K,

Φ

100mm

×

22mm (diameter

×

thickness),

Φ4.

5mm and 44mm

65mm respectively.

Отзывы: