Refer to:
‘Installation Instructions for SMD, SMDR and SSSMD
Series Leakage Rated Smoke Dampers’ (Part #461338)
or
‘Installation Instructions for CFSD Series Corridor Ceiling
Dampers’ (Part #461335)
or
‘Installation Instructions for FSD, DFD, and SSFSD
Series Combination Fire Smoke Dampers’ (Part
#481318) and FSD-3XXV series (Part # 461666) for
additional details.
Notes
1.
Mininum air velocity for smoke detector operation is 100 fpm (2.5 m/s). Maximum is 4000 fpm (20.3 m/s).
2.
Since the smoke detector is not rated for use at velocities below 100 fpm (2.5 m/s), local code may require an
alternate means of damper closure such as zone detection or automated damper closure when the system fan is
shut down. The local authority having jurisdiction should be consulted prior to the installation of the damper and
smoke detector.
3.
Holes on sampling tube must face into airstream.
4.
Smoke detector specifications are:
Operating temperature range: -4°F to 158°F
(-20°C to 70°C)
Operating humidity range: 10% to 95% R.H.
Operation voltage: 24 VAC/DC or 120 VAC (50/60 Hz)
5.
Refer to System Sensor, DUCTSD Installation and Maintenance Instructions for further installation details.
6.
Refer to System Sensor, DUCTSD, Installation and Maintenance Instructions for maintenance and field tests.
7.
System Sensor
3825 Ohio Avenue
St. Charles, Illinois 60174
Phone:1-800-SENSOR2
Fax: 1-630-377-6495
Website: http://www.systemsensor.com
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards (see
complete marking on product)”
Standard 555 (Listing #R13317)
Standard 555S (Listing #R13447)
2.67 in.
9.14 in.
7.73 in.
Square
®
482753 DUCTSD Smoke Detector
1
®
Document 482753
Duct SD Smoke Detector