M2L 3000 Series VFD
98
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
84
Precharge
timeout fault
The fault is triggered if the cell
capacitors do not charge to 90% of
nominal within 30 seconds of first
applying control power, or after resetting
of a fault.
Verify that all upstream switchgear for the
medium voltage supply to the drive is closed.
Reset the fault, then monitor capacitor
voltages on the Cell Status screen as the
drive attempts to precharge. If there is only
one cell with capacitors that are not charging
like the others, replace that cell.
If medium voltage is available to the drive,
and none of the cell capacitors charge, then
the Precharge Board is not closing its
precharge relays. The Precharge Board
receives the command to close its relays
from Digital Output 1 on the Remote IO block
by a 120VAC signal on wire 50.
Verify that Digital Output 1 is receiv-
ing 120VAC on wire 6B
Verify that Digital Output 1 closes
during precharge, and supplies
120VAC on wire 50
If the LED on Digital Output 1 indi-
cates that it is closed, but does not
supply 120VAC on wire 50, the digi-
tal output may have failed. Replace
the digital output module.
If Digital Output 1 is functioning normally, the
Precharge Board may have failed, or there
may be a loose connection to the Precharge
Board. Be sure to remove Medium Voltage
and allow time for the cell capacitors to
discharge before accessing the Precharge
Board.
Verify that wires 50 and 7 are se-
curely connected to the Precharge
Board
Verify that the thick white wires are
securely connected to the main con-
tactor tabs and studs on the Pre-
charge Board.
If all wires are securely connected,
the Precharge Board may have
failed. Replace the Precharge Board.
If medium voltage is available to the drive,
the drive has multiple Precharge Boards in
parallel, and all of the cells charge to a value
that is only a fraction of the expected voltage
before the Precharge timeout fault occurs,
one of the multiple precharge circuits may
have a loose connection, or failed
component. Follow the same troubleshooting
steps outlined above.
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...