Power Wiring
Input Line Requirements
The input line source needs to be an adequate source to start the motor, generally 2 times the rating of the motor
FLA. (This may not apply in some cases such as being connected to a generator).
Recommended Wire Gauges
The wire gauge selection is based on the FLA of the motor. Refer to NEC table 310, 60 or CEC Part 1, Table 2 or
local code requirements for selecting the correct wire sizing. Ensure appropriate wire derating for temperature is
applied. In some areas local codes may take precedence over the NEC or CEC. Refer to your local requirements.
Power Wire Connections
Attach the motor cables:
• Use the T1, T2 and T3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the
customer).
Attach the power source cables:
• Use the L1, L2 and L3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the
customer).
Compression Lugs
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for copper
wire
.
Table 14: Single Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0S20
500 MCM
BLU-050S2
2/0
BLU-2/0S4
600 MCM
BLU-060S1
3/0
BLU-3/0S1
650 MCM
BLU-065S5
4/0
BLU-4/0S1
750 MCM
BLU-075S
250 MCM
BLU-025S
800 MCM
BLU-080S
300 MCM
BLU-030S
1000 MCM
BLU-100S
350 MCM
BLU-035S
1500 MCM
BLU-150S
400 MCM
BLU-040S4
2000 MCM
BLU-200S
450 MCM
BLU-045S1
Table 15: Two Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0D20
500 MCM
BLU-050D2
2/0
BLU-2/0D4
600 MCM
BLU-060D1
3/0
BLU-3/0D1
650 MCM
BLU-065D5
4/0
BLU-4/0D1
750 MCM
BLU-075D
250 MCM
BLU-025D
800 MCM
BLU-080D
300 MCM
BLU-030D
1000 MCM
BLU-100D
350 MCM
BLU-035D
1500 MCM
BLU-150D
400 MCM
BLU-040D4
2000 MCM
BLU-200D
450 MCM
BLU-045D1
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...