Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
600
Interlock fault
C,S
Occurs when digital input 1 on the
Computer Card stops receiving 24
VDC.
Verify that the 24 VDC power supply is
functioning. If not, check the fuse supplying
its input power.
Verify that 24VDC is present across
terminals I/O4 and I/O3 on the breakout
board for the Computer Card IO.
If no devices are installed in the E-stop loop,
verify the yellow jumper wire is installed
between terminals 29 and 31, and that 24
VDC is present on terminal 31.
If there are devices in the E-stop loop, verify
that they are all closed.
604
Inverter Digital Input 4
fault
D
Occurs when
Inverter
Digital Input #4
Function
(IO-03) is set to “External
Fault High”, and 120 VAC is applied to
Digital Input 4 on the Remote IO.
Occurs when
Inverter
Digital Input #4
Function
(IO-03) is set to “External
Fault Low”, and 120 VAC is removed
from Digital Input 4 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 4 on the Remote IO, broken out
to terminal 87 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 4
on the screen toggles as the 120 VAC going
into Inverter Digital Input 4 toggles. If not,
replace the digital input module in the
Remote IO block.
605
Inverter Digital Input 5
fault
D
Occurs when
Inverter
Digital Input #5
Function
(IO-04) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 5 on the Remote IO.
Occurs when
Inverter
Digital Input #5
Function
(IO-04) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 5 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 5 on the Remote IO, broken out
to terminal 88 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 5
on the screen toggles as the 120 VAC going
into Inverter Digital Input 5 toggles. If not,
replace the digital input module in the
Remote IO block.
606
Inverter Digital Input 6
fault
D
Occurs when
Inverter
Digital Input #6
Function
(IO-05) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 6 on the Remote IO.
Occurs when
Inverter
Digital Input #6
Function
(IO-05) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 6 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 6 on the Remote IO, broken out
to terminal 89 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 6
on the screen toggles as the 120 VAC going
into Inverter Digital Input 6 toggles. If not,
replace the digital input module in the
Remote IO block.
607
Inverter Digital Input 7
fault
D
Occurs when
Inverter
Digital Input #7
Function
(IO-06) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 7 on the Remote IO.
Occurs when
Inverter
Digital Input #7
Function
(IO-06) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 7 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 7 on the Remote IO, broken out
to terminal 90 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 7
on the screen toggles as the 120 VAC going
into Inverter Digital Input 7 toggles. If not,
replace the digital input module in the
Remote IO block.
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...