Drive Enable / Drive Disable
- For use with external control logic, all Drive Enable in-
puts must be on, and all Drive Disable inputs off, for the drive to run. If a Drive Enable in-
put is removed while the motor is running, the motor will coast to a stop.
10:
Input Phase Fault
- For use with an external incoming line voltage protection relay, if
this input goes high, the drive will fault.
11:
Transformer Fault
- For use with protection switches on a remotely located front end
transformer, such as applications monitoring pressure or level switches of an oil-filled
transformer. If this input goes low, the drive will fault.
12:
Transformer Warning
-Also for use with protection switches on a remotely located
front end transformer. If this input goes low, the drive will indicate a warning.
13:
Converter Warning
- For use with protection switches in the Convertor or rectifier sec-
tion. If this input goes low, the drive will indicate a warning.
14:
Converter Fault
- Also for use with protection switches in the Converter or rectifier
section. If this input goes low, the drive will fault.
15:
Main Contactor Feedback
- For internal control logic only. The drive uses this input to
monitor the main contactor in the Inverter section.
16:
Output Contactor Feedback
- When there is an output contactor controlled by the
drive with a digital output programmed as “Output Contactor Control”, a digital input
should be programmed to monitor feedback from its normally open auxiliary contact.
17:
Input Disconnect Feeback
– When there is an input disconnect switch, a digital input
should be programmed to monitor feedback from its normally open auxiliary contact.
18:
Output Disconnect Feedback
– When there is an output disconnect switch, a digital
input should be programmed to monitor feedback from its normally open auxiliary con-
tact.
19:
DC Link Rector Warning
– When there is a DC link reactor, a digital input should be
programmed to monitor its normally closed temperature warning switch.
20:
DC Link Ractor Fault
– When there is a DC link reactor, a digital input should be pro-
grammed to monitor its normally close temperature trip switch.
21:
Output Reactor Warning
– When there is an output reactor, a digital input should be
programmed to monitor its normally closed temperature warning switch.
22:
Output Reactor Fault
– When there is an output reactor, a digital input should be pro-
grammed to monitor its normally closed temperature trip switch.
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...