8 – Fault Conditions
117
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
701
Converter fault
C,S
Occurs when 120 VAC is removed
from
Digital Input 2
on the Remote IO.
Digital Input 2 on the Remote IO is intended
to monitor failsafe (normally closed)
temperature switches in the converter
section of the drive.
It is intended for Digital Input 2 on the
Remote IO to monitor failsafe (normally
closed) protective devices such as
temperature or airflow switches in the
converter section of the drive, or the
combined transformer and converter section
of the drive. Determine if those switches
have tripped or have malfunctioned.
Verify that 120 VAC is being supplied to
those switches. If not, check the input fuse
and output fuse of the 120 VAC control
power transformer (T3).
This could be caused by digital inputs on the
Remote IO other than Digital Input 2 being
programmed as a “Converter Fault Low”
input. Check settings for
Digital Input #4
Function
(IO-03) through
Digital Input #8
Function
(IO-07) and verify that none are set
to “Converter Fault”.
Verify that all fans for the converter cabinet
are working. Check and replace fuses as
necessary.
Verify that the filters for the converter cabinet
are not clogged. Clean as necessary.
702
Ground Current fault
C,S
Occurs when excessive ground
currents are detected.
The ground fault current is detected by a
circuit on the Precharge Board in the power
wire connection section of the inverter. The
circuit produces a bi-polar signal that is
connected to Analog Input 1 on the Remote
IO. A ground fault is declared when the
absolute value of the level on that input
exceeds 5V.
Open the inverter and visually inspect to
ensure that no wires are touching any of the
cells.
Visually inspect power wiring including the
DC bus and motor leads. Pay particular
attention to any splices that may be in the
motor leads.
Disconnect the motor leads from the drive
and Megger the motor through the motor
leads. Use a megaohm meter / insulation
tester capable of producing the motor’s rated
voltage.
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...