M2L 3000 Series VFD
100
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
201
GPP initialization
of DSP fault
F
Occurs if the general purpose processor
on the Computer Card is unable to
initialize the digital signal processor on
the Computer Card after control power
is first applied.
Contact Benshaw
202
GPP initialization
fault monitor
F
Occurs if the general purpose processor
is unable to initialize some of its
processes after control power is first
applied.
Contact Benshaw
203
GPP initialization
of backplane fault
F
Occurs if the general purpose processor
on the Computer Card cannot initialize
the FPGA (which communicates to the
Fiber Optic Boards) over the backplane
after control power is first applied.
Contact Benshaw
204
PCI FPGA
initialization fault
F
Occurs if the general purpose processor
on the Computer Card cannot initialize
the FPGA (which communicates over
the PCI bus) over the backplane after
control power is first applied.
Contact Benshaw
205
FOB initialization
fault
F
Occurs if the Computer Card is unable
to initialize the Fiber Optic Boards after
control power is first applied.
Contact Benshaw
206
Cell initialization
fault
F
Occurs if the Computer Card is unable
to initialize the cells after control power
is first applied.
Refer to the specific cell faults.
207
HTTP server
initialization fault
F
Occurs if the Computer Card is unable
to create a task for the HTTP server
after control power is first applied.
Contact Benshaw
208
FTP Server
initialization fault
F
Occurs if the Computer Card is unable
to create a task for the FTP server after
control power is first applied.
Contact Benshaw
209
Missing drive
parameters fault
Occurs if the Computer Card is unable
to retrieve parameters from the SD card
because it could not find the file used to
store parameters.
Remove the Computer Card to verify that the
SD card is present, and securely inserted in
the SD card slot in the Computer Card.
If the SD card has failed, obtain a
replacement from Benshaw, part number
SD-100000-00. Do not use an off-the-shelf
commercial SD card, as they are typically not
rated for harsh environments.
210
Invalid drive
parameters fault
Occurs if the Computer Card is unable
to retrieve parameters from the SD card
because the contents of the file used to
store parameters are unexpected or
corrupted.
After detecting invalid drive parameters on
the SD card, the Computer Card will set all
parameters to their default values and
overwrite the file on the SD card. Use the
HMI or Benshaw Connect to set parameter
values to the required values.
Contact Benshaw to determine if further
action is necessary.
211
Real Time Clock
initialization fault
Occurs if the Computer Card is unable
to initialize some of its processes or is
unable to establish communications with
its real time clock chip.
Contact Benshaw
Содержание M2L 3000
Страница 2: ...M2L 3000 Series VFD 2...
Страница 6: ...M2L 3000 Series VFD 6...
Страница 10: ...M2L 3000 Series VFD 10...
Страница 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Страница 15: ...1 Introduction 15 NOTE Only the 260A and 300A models are presently available as UL listed models...
Страница 16: ...M2L 3000 Series VFD 16...
Страница 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Страница 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Страница 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Страница 40: ...M2L 3000 Series VFD 40...
Страница 72: ...M2L 3000 Series VFD 72...
Страница 124: ...M2L 3000 Series VFD 124...
Страница 126: ...M2L 3000 Series VFD 126...
Страница 127: ...References 127 References Placeholder for text with left side label...
Страница 128: ...M2L 3000 Series VFD 128...
Страница 132: ...M2L 3000 Series VFD 132...
Страница 139: ...Revision History 139 Revision History Revision Date ECO Description 00 December 15 2017 E5306 Initial Release...