Commissioning, settings and testing
22
5.2 Assigning addresses-examples
Please also note the information in the "BMS bus" instruction leaflet. * The settings for the
alarm addresses marked with an asterisk (*) refer to reciprocal monitoring of MK... alarm in-
dicator and test combinations.
A changeover and monitoring module with two alarm indicator and test combinations:
Two changeover and monitoring modules, with two alarm indicator and test combinations each:
Device
Parameters
Address settings for a changeover module
107TD47
Bus address
3
PRC487
Address
4
First MK...
Address
1
Test address
3
Alarm address
3, 4, 2
*
Second MK...
Address
2
Test address
3
Alarm address
3, 4, 1
*
Device
Parameters
Address settings for the first
changeover module
Address settings for the
second changeover module
107TD47
Bus address
5
7
PRC487
Address
6
8
First MK...
Address
1
3
Test address
5
7
Alarm address
5, 6, 2
*
7, 8, 4
*
Second MK...
Address
2
4
Test address
5
7
Alarm address
5, 6, 1
*
7, 8, 3
*
UMC...
MK... MK...