Trouble shooting
23
6. Trouble shooting
6.1 PRC487 error messages
If a fault occurs, the MEDICS
®
system messages will enable you to narrow down the possible
causes. Some messages can have several causes. The following possible errors are indicated
by messages in the PRC487 display.
If you cannot trigger a test function on the PRC487, an alarm message may already be pend-
ing, or there may be an open circuit at terminal 9-Ub of the PRC487.
PRC message
Possible causes
Failure line 1
Power supply failure on line 1. SUE487 failure. Open circuit, ter-
minal 6-GND3. Defective fuse 1-L1, 1-L2.
Failure line 2
Power supply failure on line 2. SUE487 failure. Open circuit, ter-
minal 5-GND3. Defective fuse 2-L1, 2-L2.
Failure distribution
board
Power supply failure downstream of the changeover module.
SUE487 failure. Open circuit terminal 4-GND3
Failure K3
Failure of the internal relay K3 (SUD487). Open circuit terminal
IN3-GND3
K1/2 manual mode
Contactor control has been changed to manual mode. Auto-
matic changeover will no longer be performed!
Short-circuit distri-
bution board
Short-circuit downstream of changeover module. Following a
failure on line 1 and changeover to line 2, line 2 drops out and
voltage is present on line 1 again.
Wire break K1 on
Open circuit when controlling K1 via terminals 11/14 of the
PRC487, auxiliary contact K2 or resistor R1.
Wire break K1 off
Open circuit when controlling K1 via terminals 21/24 of the
PRC487 for the purpose of shutting down the latching module.
Wire break K2 on
Open-circuit when controlling K2 via terminals 31/34, auxiliary
contact K1 or resistor R2.
Wire break K2 off
Open circuit when controlling K2 via terminals 41/44 of the
PRC487 for the purpose of shutting down the latching module.
Fault K1 on
K1 cannot be activated. K1 is jammed. Open circuit, auxiliary
contact at terminal GND1 or IN1 of PRC487.
Fault K1 off
K1 cannot be switched off via latching module. K1 is jammed.
Open circuit, auxiliary contact at terminal GND1 or IN1 of
PRC487.
Fault K2 on
K2 cannot be activated. K2 is jammed. Open circuit, auxiliary
contact at terminal GND2 or IN2 of PRC487.
Fault K2 off
K2 cannot be deactivated via latching module. K2 is jammed.
Open circuit, auxiliary contact at terminal GND2 or IN2 of
PRC487.
Failure K1
K1 on, but no voltage downstream of K1. Open circuit, main
contacts K1 or line upstream or downstream of K1. SUE487 fail-
ure.
Содержание MEDICS UMC107E Series
Страница 18: ...Installation and connection 18 TGH1322en 06 2009 4 2 2 Wiring diagram Fig 4 1 Wiring diagram UMC107E...
Страница 19: ...Installation and connection 19 TGH1322en 06 2009 4 2 3 Circuit diagram Fig 4 2 Circuit diagram UMC107E...
Страница 32: ...Manufacturer s certificate checklist circuit documentation 32 TGH1322en 06 2009...
Страница 34: ...INDEX TGH1322en 06 2009...
Страница 35: ......