99
I20683 - Subject to change.
Installation and Operation
Non-Spring Return
General Information
If more torque is required than one TGMB can provide, TGMB24-SR may be installed on the same shaft.
Multiple Actuator Mounting
Preliminary Steps
1.
Belimo actuators with NEMA 1 or NEMA 2 ratings should
be mounted indoors in a dry, relatively clean environment
free from corrosive fumes. If the actuator is mounted out-
doors, a protective enclosure must be used to shield the
actuator.
2.
For new construction work, order dampers with extended
shafts. Instruct the installing contractor to allow space for
mounting the Belimo actuator on the shaft.
For replacement of existing gear train actuators, there are two
options:
A.
From a performance standpoint, it is best to mount the
actuator directly onto the damper shaft.
B.
If the damper shaft is not accessible, mount the non-
spring return actuator with a ZG-NMA or ZG-GMA
crankarm kit, and a mounting bracket (ZG-100, ZG-
101, ZG-103, ZG-104)
Determining Torque Loading and Actuator Sizing
Damper torque loadings, used in selecting the correct size actuator, should be provided by the damper manufacturer.
If this information is not available, the following general selection guidelines can be used.
Damper Type
Torque Loading
Opposed blade, without edge seals, for non-tight close-off applications
3 in-lb/sq. ft.
Parallel blade, without edge seals, for non-tight close-off applications
4 in-lb/sq. ft.
Opposed blade, with edge seals, for tight close-off applications
5 in-lb/sq. ft.
Parallel blade, with edge seals, for tight close-off applications
7 in-lb/sq. ft.
The above torque loadings will work for most applications under 2 in. w.g. static pressure or 1000 FPM face velocity.
For applications between this criteria and 3 in. w.g. or 2500 FPM, the torque loading should be increased by a multiplier
of 1.5. If the application calls for higher criteria up to 4 in. w.g. or 3000 FPM, use a multiplier of 2.0.
Table of Contents
Page
General Mounting
❑
Standard ............................................100
❑
Reversible Clamp ..............................101
❑
Retrofit Brackets ................................102
Operation
❑
Electrical ............................................103
❑
Mechanical..........................................104
Wiring
❑
General ..............................................105
❑
Accessories ........................................106
Startup and Checkout ..................................109
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...