Wiring Diagrams
95
I20683 - Subject to change.
TLMB
24 VAC Transformer
a open
a closed
The indication of direction
is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
a
Line
Volts
–
1
0
2
3
5
TLMB24-3
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
TLMB24-3 (-T)
On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V
TLMB24-3 - Typical Specification:
Floating point, on/off control damper actuators shall be
electronic direct-coupled type, which require no crankarm
and linkage and be capable of direct mounting to a shaft
from 1/4” to 5/8”. Shafts up to 3/4” diameter can be
accommodate with an accessory clamp. Actuators shall
have brushless DC motor technology and be protected
from overload at all angles of rotation. Actuators shall have
reversing switch and manual override on the cover. If
required, actuator will be provided with screw terminal strip
for electrical connections (TLMB24-3-T). Run time shall be
constant and independent of torque. Actuators are cULus
listed, and be manufactured under ISO 9001 International
Quality Control Standards. Actuators shall be as
manufactured by Belimo.
W500
24 VAC Transformer
The indication of direction
is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
Line
Volts
–
1
0
2
3
5
TLMB24-3
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W501
On/Off
Floating point or On/Off control
CAUTION
2
Equipment damage!
Up to 4 actuators may be connected in parallel.
With 4 actuators wired to one 500
Ω
resistor.
Power consumption must be observed and input
impedance must be observed.
APPLICATION NOTES
Meets cULus or UL and CSA requirements without
the need of an electrical ground connection.
INSTALLATION NOTES
3
5
Actuator may also be powered by 24 VDC.
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables use numbers.
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...