TLF24 (-S)
On-off, Spring Return Fail-Safe, 24 V
Torque min. 35 in-lb, for control of air dampers
Application
For on-off, fail-safe control of dampers in HVAC systems.
Actuator sizing should be done in accordance with the damper
manufacturer’s specifications. Control is on-off from an
auxiliary contact, digital output, or a manual switch.
The actuator is mounted directly to a damper shaft from 3/8”
up to 1/2” in diameter by means of its universal clamp, 1/2”
shaft centered at delivery. For shafts up to 3/4” use K6-1
accessory. A crank arm and several mounting brackets are
available for applications where the actuator cannot be direct
coupled to the damper shaft.
Operation
The TLF series actuators provide true spring return operation
for reliable fail-safe application and positive close off on air tight
dampers. The spring return system provides consistent torque
to the damper with, and without, power applied to the actuator.
The TLF series provides 95° of rotation and is provided with a
graduated position indicator showing 0° to 95°. The actuator
may be stalled anywhere in its normal rotation without the
need of mechanical end switches. Power consumption is
reduced in holding mode.
The TLF24-S version is provided with one built in auxiliary
switch. This SPDT switch is provided for safety interfacing or
signaling, for example, for fan start-up. The switching function
is adjustable between 0° and 95°. The auxiliary switch in the
TLF24-S is double insulated so an electrical ground
connection is not necessary.
For all accessories, see pages 110 and 132.
Dimensions
[All numbers in brackets are in millimeters.]
0.39" [10]
7.67" [195]
3.66" [93]
1.93"
[49]
6.10" [155]
3.15" [80]
3.86"
[98]
0.256" [6.5]
0.98"
[25]
4.92" [125]
0.79"
[20]
0.5"
[12.7]
0.71" [18]
0.74" [18.7]
2.24"
[57]
3.23" [82]
0.25" [6.3]
Standard:
3/8" to 1/2"
3/8" to 7/16"
Optional
1/2" to 3/4"
w/K6-1
accessory
Technical Data
TLF24 (-S)
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption
running: 5 W; holding: 2.5 W
Transformer sizing
7 VA (class 2 power source)
Electrical connection
3 ft, 18 GA appliance cable
(TLF24-S has 2 cables)
1/2” conduit connector
Overload protection
electronic throughout 0° to 95° rotation
Angle of rotation
max. 95°, adjust. with mechanical stop
Torque
35 in-lb [4 Nm]
Direction of rotation
reversible with cw/ccw mounting
Position indication
visual indicator, 0° to 95° (0° is spring
return position)
Auxiliary switch
1 x SPDT 6A (1.5) @ 250 VAC, UL listed
adjustable 0° to 95° (double insulated)
Running time
motor: < 40 to 75 sec
spring: < 25 sec
@-4°F to +122°F [-20°C to +50°C]
< 60 sec
@-22°F [-30°C]
Humidity
5 to 95% RH non-condensing
Ambient temperature
-22°F to +122°F [-30°C to +50°C]
Storage temperature
-40°F to +176°F [-40°C to +80°C]
Housing
NEMA type 2 / IP54
Housing material
zinc coated steel
Agency listings
UL 873 listed, CSA C22.2 No.24
certified, CE
Noise level
max:
running < 50 db (A)
spring return 62 dB (A)
Servicing
maintenance free
Quality standard
ISO 9001
Weight
TLF24
3.1 lbs (1.40 kg.)
TLF24-S 3.2 lbs (1.45 kg.)
LISTED
94D5
TEMP. IND &
REG. EQUIP
.
UL
(TLF24-S)
(nominal)
44
D010
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...