I20683 - Subject to change.
TLF
2 to 10 VDC control of TLF24-SR
TLF24-SR
Proportional Damper Actuator, Spring Return Fail-Safe, 24 V for 2 to 10 VDC, or 4 to 20 mA Control Signal.
Output Signal of 2 to 10 VDC for Position Indication.
TLF24-SR Typical Specification
Spring return control damper actuators shall be direct coupled
type which require no crankarm and linkage and be capable of
direct mounting to a shaft up to a 3/4” diameter and center a
1/2” shaft. The actuator must provide proportional damper
control in response to a 2 to 10 VDC or, with the addition
of a 500
Ω
resistor, a 4 to 20 mA control input from an
electronic controller or positioner.The actuators must be
designed so that they may be used for either clockwise or
counterclockwise fail-safe operation. Actuators shall use a
brushless DC motor controlled by a microprocessor and be
protected from overload at all angles of rotation. Run time
shall be constant, and independent of torque. A 2 to 10 VDC
feedback signal shall be provided for position feedback or
master-slave applications. Actuators are UL listed and CSA
certified and be manufactured under ISO 9001 International
Quality Control Standards. Actuators shall be
as manufactured by Belimo.
Wiring Diagrams
1
6
5
2
3
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input,
2 to
10V
Grn (5) U
Output,
2 to
10V
TLF24-SR
Line
Volts
2 to 10 VDC
Control Signal (–)
(+)
CW CCW
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
To other
actuators
6
3
5
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input,
2 to 10V
Grn (5) U Output,
2 to 10V
4 to 20 mA
Control Signal
(–)
(+)
2 to 10 VDC
Feedback Signal
(–)
(+)
Ω
500
Ω
2
TLF24-SR
CW CCW
Line
Volts
1
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
4 to 20 mA control of TLF24-SR with 2 to 10 VDC
feedback output
W465
W466
CAUTION
2
Equipment damage!
Up to 4 actuators may be connected in parallel.
With 4 actuators wired to one 500
Ω
resistor.
Power consumption must be observed and input
impedance must be observed.
APPLICATION NOTES
Meets cULus or UL and CSA requirements without
the need of an electrical ground connection.
The ZG-R01 500
Ω
resistor converts the 4 to 20 mA
control signal to 2 to 10 VDC.
INSTALLATION NOTES
3
5
6
Actuator may also be powered by 24 VDC.
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables use numbers.
Only connect common to neg. (—) leg of control
circuits. The TLF24-SR wire 5 is white.
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...