I20683 - Subject to change.
TLF24-3
On-off, Spring Return Fail-Safe, Reversible, Floating Point, 24V
Torque min. 35 in-lb, for control of air dampers
Application
For modulation or on-off control of dampers in HVAC systems.
Actuator sizing should be done in accordance with the damper
manufacturer’s specifications.
The actuator is mounted directly to a damper shaft from 3/8”
up to 1/2” in diameter by means of its universal clamp, 1/2”
shaft centered at delivery. For shafts up to 3/4” use K6-1
accessory. A crank arm and several mounting brackets are
available for applications where the actuator cannot be direct
coupled to the damper shaft.
Control is floating point from a triac or relay, or on-off from an
auxiliary contact from a fan motor contactor, controller, or
manual switch.
Operation
The TLF series actuators provide true spring return operation
for reliable fail-safe application and positive close-off on air tight
dampers. The spring return system provides consistent torque
to the damper with, and without, power applied to the actuator.
The TLF series provides 95° of rotation and is provided with a
graduated position indicator showing 0° to 95°.
The TLF24-3 uses a brushless DC motor which is controlled by
an Application Specific Integrated Circuit (ASIC) and a micro-
processor. The microprocessor provides the intelligence to the
ASIC to provide a constant rotation rate. The ASIC monitors
and controls the brushless DC motor’s rotation and provides a
digital rotation sensing function to prevent damage to the actua-
tor in a stall condition. The actuator may be stalled anywhere in
its normal rotation without the need of mechanical end switches.
Power consumption is reduced in holding mode.
For all accessories, see pages 110 and 132.
Dimensions
[All numbers in brackets are in millimeters.]
Technical Data
TLF24-3
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption
running: 2.5 W; holding: 1 W
Transformer sizing
5 VA (class 2 power source)
Electrical connection
TLF24-3 3 ft, plenum rated cable
Overload protection
electronic throughout 0° to 95° rotation
Input impedance
1000
Ω
(0.6w) control inputs
Angle of rotation
max. 95°, adjust. with mechanical stop
Torque
35 in-lb [4 Nm]
Direction of rotation
spring: reversible with cw/ccw mounting
motor: reversible with built-in switch
Position indication
visual indicator, 0° to 95° (0° is spring
return position)
Running time
motor: 150 sec constant,
independent of load
spring: < 25 sec
@-4°F to +122°F [-20°C to +50°C]
< 60 sec
@-22°F [-30°C]
Humidity
5 to 95% RH non-condensing
Ambient temperature
-22°F to +122°F [-30°C to +50°C]
Storage temperature
-40°F to +176°F [-40°C to +80°C]
Housing
NEMA type 2 /IP54
Housing material
zinc coated metal
Agency listings
UL 873 listed; CSA C22.2 No. 24
certified, CE
Noise level
max:
running < 30 db (A)
spring return 62 dB (A)
Servicing
maintenance free
Quality standard
ISO 9001
Weight
TLF24-3 3.1 lbs (1.40 kg.)
LISTED
94D5
TEMP. IND &
REG. EQUIP
.
UL
46
0.39" [10]
7.67" [195]
3.66" [93]
1.93"
[49]
6.10" [155]
3.15" [80]
3.86"
[98]
0.256" [6.5]
0.98"
[25]
4.92" [125]
0.79"
[20]
0.5"
[12.7]
0.71" [18]
0.74" [18.7]
2.24"
[57]
3.23" [82]
0.25" [6.3]
Standard:
3/8" to 1/2"
3/8" to 7/16"
Optional
1/2" to 3/4"
w/K6-1
accessory
D010
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...