159
I20683 - Subject to change.
Wiring Guide
Wiring Diagrams
IV-E. Accessories
Feedback Potentiometer
P…A GR used with TGM / TAM / TNM / TLM
2
To other
actuators
●
●
●
●
24 VAC Transformer
Line
Volts
Control
Signal
1
Common
2
+ Hot
3
Signal Input
4
Output, 2 to 10 VDC
IRM-100
1
1
Line
Volts
1
Common
2
+ Hot
3
Y
1
4
Y
2
5
U
…-SR
US
(–)
(+)
●
●
3
2
1
Provide overload protection and disconnect as required.
The controller should be powered from a separate
transformer.
The actuator and IRM-100 may be powered from the
same transformer.
Consult controller instruction data for more detailed
installation information.
To reverse control rotation, use the reversing switch.
3
4
5
5
4
IRM-100 Input Rescaling Module
●
●
●
24 VAC Transformer
Line
Volts
1
Common
2
+ Hot
3
Signal Input
4
Contactor
5
Ref. signal
6
Contactor
7
Ref. signal
8
Contactor
9
Ref. signal
ADS-100
COM
∩ ∩
∩
∩ ∩
∩
∩ ∩
∩
Reheat output
(2 to 10 VDC)
from TRS-M
thermostat or
other controller
Reheat stage
(24 VAC con-
tactors 10 VA
max. per stage)
5,7,9 = Switch point reference signal for manual
adjustment of stages 1,2, & 3 respectively.
Actuator and controller must have separate transformers.
Stage 1
#1
#2
#3
1
1
}
Stage 2
}
Stage 3
}
2
(–)
(+)
2
●
●
●
ADS-100 Analog to Digital Switch
●
2
4
●
●
●
●
●
●
●
24 VAC Transformer
U 2 to 10 VDC
Feedback signal
0 to 20 V Phasecut
Line
Volts
1
Common
2
+ Hot
3
Y
1
4
Y
2
5
U
6 Z
1
Common
2
+ Hot
3
Y
1
5
U
1
Common
2
+ Hot
3
Y
1
5
U
(–)
(+)
Control Signal
0 to 10 VDC
2
1
A
B
C
Override
Switch Position
A = Closed
B = Normal
C = Open
…-SR
US
SBG24
I
N
P
U
T
O
U
T
P
U
T
3
5
SBG 24 Range Controller
SGA, SGF Positioners
Remote Control
P1
P2
P3
P…A GR
0
10
●
●
24 VAC Transformer
Line
Volts
1
Common
2
+
3
+ Y
…-SR
A
B
●
1
Common
2
+
3
Y
4 Z
SGA24 SGF24
●
●
●
●
●
●
●
24 VAC
Transformer
Line
Volts
1
Common
2
+
3
Y
. . -SR
1
Common
2
+
3
Y
4 Z
SGA24 SGF24
(–)
(+)
0 to 10 VDC
Control Signal
A
B
off
off
0%
off
on
0%
on
off
0 to 100%
on
on
100%
Override control
Damper control
Minimum Position Setting
Provide overload protection and disconnect as required.
Override switches are optional.
1
1
1
2
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power con-
sumption and input impedance must be observed.
The actuator and SBG-24 may be powered from the
same transformer.
The controller should be powered from a separate
transformer.
Wire No. 4 on the TNM24-SR is used for feedback.
1
2
3
4
5
2
2
…SR
…SR
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...