I20683 - Subject to change.
Torque min. 18 in-lb, for control of air dampers
Application
For on-off, fail-safe control of dampers in HVAC systems.
Actuator sizing should be done in accordance with the damper
manufacturer’s specifications. Control is on-off from an
auxiliary contact, or a manual switch.
The actuator is mounted directly to a damper shaft from 1/4”
up to 1/2” in diameter by means of its universal clamp, 1/2”
shaft centered at delivery. A crank arm and several mounting
brackets are available for applications where the actuator
cannot be direct coupled to the damper shaft.
Operation
The TTF series actuators provide true spring return operation
for reliable fail-safe application and positive close off on air tight
dampers. The spring return system provides consistent torque
to the damper with, and without, power applied to the actuator.
The TTF series provides 95° of rotation and is provided with a
graduated position indicator showing 0° to 90°.
The actuator may be stalled anywhere in its normal rotation
without the need of mechanical end switches. Power
consumption is reduced in holding mode.
The TTF24-S versions are provided with one built-in
auxiliary switch. This SPDT switch is provided for safety
interfacing or signaling, for example, for fan start-up. The
switching function is adjustable between 0° and 95°.
For all accessories, see pages 110 and 132.
Dimensions
[All numbers in brackets are in millimeters.]
TTF24 (-S)
On-off, Spring Return Fail-Safe, 24V
Technical Data
TTF24 (-S)
Power supply
24VAC ± 20%, 50/60Hz
24VDC ± 10%
Power consumption
running: 2.5 W
holding: 1.3 W
Transformer sizing
5 VA (class 2 power source)
Electrical connection
3 ft, 18 GA appliance cable
(-S models have 2 cables)
1/2” conduit connector
Overload protection
electronic throughout 0° to 95° rotation
Angle of rotation
max 95°, adjust. with mechanical stop
Torque
min. 18 in-lb [2 Nm]
Direction of rotation
reversible with cw/ccw mounting
Position indication
visual indicator, 0° to 95°
(0° spring return position)
Auxiliary switch
1 x SPDT 3A (0.5A) @ 250 VAC,
(-S models)
UL listed adjustable 0° to 95°
Running time
motor: < 75 sec (0 to 18 in-lb)
spring:< 25 sec
@-4°F to +122°F [-20°C to +50°C]
< 60 sec
@-22°F [-30°C]
Humidity
5 to 95% RH non-condensing
Ambient temperature
-22°F to +122°F [-30°C to +50°C]
Storage temperature
-40°F to +176°F [-40°C to +80°C]
Housing
NEMA type 2 / IP42
Housing material
UL94 - 5VA
Agency listings
cULus listed acc. to UL 60730-1
Noise level
max: running < 50 db (A)
spring return 62 dB (A)
Servicing
maintenance free
Quality standard
ISO 9001
Weight
TTF24
1.4 lbs (0.6 kg)
TTF24-S 1.5 lbs (0.7 kg)
(nominal)
0.43" [11]
0.77" [19.5]
4.5"
[114]
0.2"
[5.2]
1.57"
[40]
6.28"
[159.5]
3.0"
[76.2]
3.30"
[83.72]
2.40"
[61]
0.68" [16.7]
Standard:
1/4" to 1/2"
1/4" to 5/16"
Safety Note
Screw a conduit fitting into the actuator’s bushing. Jacket the
actuator’s input and output wiring with suitable flexible conduit.
Properly terminate the conduit in a suitable junction box.
D096
60
Содержание TRANE TAF Series
Страница 7: ...Notes Work Pad 7 I20683 Subject to change...
Страница 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Страница 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Страница 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Страница 98: ...98 I20683 Subject to change Notes Work Pad...
Страница 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Страница 166: ...Notes Work Pad 166 I20683 Subject to change...
Страница 167: ...167 I20683 Subject to change Notes Work Pad...