Installation EAGLE20/30
Release 11 09/2020
35
For the supply voltage to be connected, perform the following steps:
Remove the power connector from the device.
Connect the wires according to the pin assignment on the device with the
clamps.
Fasten the wires connected by tightening the terminal screws.
2.5.2
Supply voltage with the characteristic value KK
You have the option of supplying the supply voltage redundantly, without
load distribution.
Both supply voltage inputs are uncoupled.
With a redundant supply, the supply voltage 1 (upper voltage input on the
device) has priority.
Figure 7: Supply voltage with the characteristic value KK: 3-pin terminal block with
screw locking
For
every
supply voltage to be connected, perform the following steps:
Remove the power connector from the device.
Connect the wires according to the pin assignment on the device with the
clamps.
Fasten the wires connected by tightening the terminal screws.
With a non-redundant supply of the supply voltage, the device reports the
loss of a supply voltage. You can prevent this message by applying the
supply voltage via both inputs, or by changing the configuration in the
Management.
Type of the voltages
that can be
connected
Specification of the supply
voltage
Connections
DC voltage
Rated voltage range DC
60 V ... 250 V
Voltage range DC incl.
maximum tolerances
48 V ... 320 V
+/L Plus terminal of the supply voltage
−
/N Minus terminal of the supply
voltage
Protective conductor
AC voltage
Rated voltage range AC
110 V ... 230 V, 50 Hz ... 60 Hz
Voltage range AC incl.
maximum tolerances
88 V ... 265 V, 47 Hz ... 63 Hz
+/L Outer conductor
−
/N Neutral conductor
Protective conductor
N
L