30
Installation BRS20/22/30/32/40/42/50/52
Release 06 03/2020
1.6
Display elements
1.6.1
Device state
These LEDs provide information about conditions which affect the operation
of the whole device.
Figure 1: LED display elements for device status
LED
Display
Color Activity
Meaning
Power Supply voltage
—
none
Supply voltages 1
and
2 are too low.
yellow lights up
Supply voltage 1
or
2 is on
flashes 4 times
a period
Software update is running. Maintain the
power supply.
green lights up
Supply voltage 1
and
2 is on
Status Device Status
—
none
Device starts
Device is not ready for operation
green lights up
Device is ready for operation
Characteristics can be configured
red
lights up
Device is not ready for operation
flashes 1 time
a period
The boot parameters used when the
device has been started differ from the
boot parameters saved.
Start the device again.
flashes 4 times
a period
Device has detected a multiple IP address
red/
green
flashing
alternately
Device is in the recovery mode.
ACA
Storage medium
ACA22-USB-C
(EEC)
—
none
No ACA connected
green lights up
ACA is plugged
flashes 3 times
a period
Device writes to/reads from the storage
medium
yellow lights up
ACA is not ready for operation
PoE
—
none
Supply voltage is too low
yellow lights up
Supply voltage is too low for PoE support.
green lights up
PoE voltage is on
Table 4:
Meaning of the device display elements
Power
Status
ACA
Power
Status
ACA
PoE
IP-ADDRESS
ACA
PoE
Status
Power
1
3
2
4
5
6
7
8
USB
P
0V
0V
+54V(P2)
+54V(P1)
RELA
Y