GT-650/GT-900 User's Manual
57
Tests (TC#)
400
410
411
412
413
AUTO-TEST names (default)
CORD
PRCD
PRCD-S
PRCD-S+
PRCD-K
Producer Any
Kopp
Kopp
PCE
Kopp
Visual Inspection
Yes
Yes
Yes
Yes
Yes
R
PE 200mA
(
)
0.30 0.30 0.30 0.30 -
R
INS 500V
at input side
(M
)
1.00 - - 0.20 -
R
INS 500V
at output side
(M
)
- 1.00 1.00 1.00 1.00
L/N
condition
Yes
- - - -
I
PE(
) + polarity
(mA)
- 3.50 3.50 3.50 3.50
I
PE(
) - polarity
(mA)
- 3.50 3.50 3.50 3.50
I
T + polarity
(mA)
- 0.50 0.50 0.50 0.50
I
T - polarity
(mA)
- 0.50 0.50 0.50 0.50
TEST button
-
Trip out
Trip out
-
Trip out
t
/I
N/2
(I
N
= 30 mA)
AC current
-
No trip
No trip
No trip
No trip
t
/I
N
(I
N
= 30 mA)
AC current
-
300 ms
300 ms
200 ms
300 ms
t
/I
N/2
(I
N
= 30 mA)
+pulsed current
-
No trip
No trip
No trip
No trip
t
/I
N
(I
N
= 30 mA)
+pulsed current
-
300 ms
300 ms
200 ms
300 ms
t
/I
N/2
(I
N
= 30 mA)
-pulsed current
-
No trip
No trip
No trip
No trip
t
/I
N
(I
N
= 30 mA)
-pulsed current
-
300 ms
300 ms
200 ms
300 ms
I
RAMP
(I
N
= 30 mA) and
t
/I
(I
N
= 30 mA)
AC current
-
(½ … 1) I
N
300 ms
(½ … 1) I
N
300 ms
(½ … 1) I
N
200 ms
(½ … 1) I
N
300 ms
L-TEST
-
Trip out
Trip out
Trip out &
Disabled
switch on
& No self
switch on
after L is
back
Trip out
N-TEST
-
Trip out
Trip out
Trip out &
Disabled
switch on
& No self
switch on
after N is
back
Trip out
PE-OFF TEST
-
-
Trip out &
disabled
switch on
Trip out &
Disabled
switch on
-
Varistor test (U at 1 mA)
-
-
-
-
15 … 25V
Voltage at PE
-
-
Switch off
& Disabled
switch on
Switch off
& Disabled
switch on
-
Voltage at ON button
-
-
Switch off
Switch off
-
Содержание GT-650
Страница 1: ......
Страница 2: ...GT 650 GT 900 User s Manual 2 ...
Страница 3: ...GT 650 GT 900 User s Manual 3 GT 650 GT 900 User s Manual ...
Страница 108: ......