Description of PRCD-Adapter
The PRCD-Adapter is intended to be used in combination with GT-900 tester only,
for testing all types of PRCDs in accordance with PRCD producer’s test instructions.
View:
Figure 6: View with control elements, connectors and marking of measurement
category (CAT)
1 ...... UPE button, to apply external voltage to input PE terminal of PRCD device
under test, as long as the button is pressed.
2 ...... Control neon lamp. It is ON when UPE button is pressed or when Probe 3
sufficiently touches ON button of the PRCD under test.
3 ...... Warning sign: Do not touch Probe 3, hazardous voltage may be applied to
it.
4 ...... Test socket “Probe 3” is an output, used to apply external voltage to ON
button of the PRCD under test.
5 ...... Warning sign: Output Probe 3, external voltage CAT II 300 V max. against
Earth
!
6 ...... Test socket “to Probe 1”, to be connected to Probe 1 of GT-900 tester when
testing PRCD-K devices.
7 ...... Warning sign: Output Probe 1, external voltage 30 V max. against earth !
8 ...... Warning sign: Use this test / mains socket for test purpose only!
9 ...... Schuko socket, to connect PRCD under test.
10 .... Schuko plug, to be connected to GT-900 tester.