M-0420 Instruction Book
7–38
Magnitude Accuracy Test
TEST SETTINGS:
Forward Power
Flow Magnitude
3.0 pu
Time Delay
1 Cycle
1. Press ENTER. The SELECT FUNCTION LED
should turn on and the unit should display
VOLTAGE RELAY
VOLT freq curr powr
C
2. Turn the knob clockwise until the unit displays
POWER RELAY
volt freq curr POWR
C
3. Press ENTER until the unit displays
DELAY FORWARD POWER
30 Cycles
4. Turn the knob counterclockwise until the
unit displays
DELAY FORWARD POWER
1 Cycle
5. Press ENTER once and then EXIT until the
unit displays
BECKWITH ELECTRIC CO.
M-0420
6. Slowly increase the input current until the
relay trips. The unit should trip at 15A ±0.1A.
7. The 32 DIRECTIONAL OVERPOWER LED
should turn on and the unit should rotate
displays
-TRGT- 06/22/93 10:19:12
Trip# = 29
-TRGT- 06/22/93 10:19:12
FORWARD OVERPOWER
8. Set the input current to 5.00 A.
9. Press TARGET RESET/LAMP TEST. The
32 DIRECTIONAL OVERPOWER LED should
turn off. The unit should display
BECKWITH ELECTRIC CO.
M-0420
–END–
32F
DIRECTIONAL POWER, FORWARD POWER, 3-PHASE
Содержание M-0420
Страница 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Страница 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Страница 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 165: ...D 1 Board Interconnections Appendix D D Board Interconnections Figure D 1 M 0420 Board Interconnections ...
Страница 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...