M-0420 Instruction Book
7–24
81U
UNDER FREQUENCY
Time Delay Accuracy Test
Test Settings:
Magnitude #1
59.50 Hz
Time Delay #1
30 cycles
9. Press ENTER. The SELECT FUNCTION LED
should turn on and the unit should display
VOLTAGE RELAY
VOLT freq curr powr
C
10. Turn the knob clockwise to highlight FREQ.
Press ENTER and then the right arrow button,
and then ENTER until the unit displays
DELAY OVERFREQUENCY #1
2 Cycles
11. Change the timer setpoint by turning the
knob clockwise to 30 cycles. The unit should
display
DELAY OVERFREQUENCY #1
30 Cycles
12. Rapidly decrease the frequency of the three-
phase test set to 59.00 Hz and start timing.
The unit should trip after 30 cycles ±1 cycle
time delay.
13. The 81 UNDERFREQUENCY LED should
turn on and the unit should rotate displays
-TRGT- 06/22/93 10:19:12
Trip# = 15
-TRGT- 06/22/93 10:19:12
UNDERFREQUENCY #1
14. Set the frequency to 60.00 Hz.
15. Press TARGET RESET/LAMP TEST. The
81 UNDERFREQUENCY LED should turn
off. The unit should display
BECKWITH ELECTRIC CO.
M-0420
—END—
Magnitude Accuracy Test
Test Settings:
Magnitude #1
59.50 Hz
Time Delay#1
2 cycles
1. Press ENTER. The SELECT FUNCTION LED
should turn on and the unit should display
VOLTAGE RELAY
VOLT freq curr powr
C
2. Turn the knob clockwise to highlight FREQ.
Press ENTER and then the right arrow button,
and then ENTER until the unit displays
DELAY OVERFREQUENCY #1
30 Cycles
3. Change the timer setpoint by turning the
knob counterclockwise to 2 cycles. The unit
should display
DELAY OVERFREQUENCY #1
2 Cycles
4. Press ENTER once and then ENTER until the
unit displays
BECKWITH ELECTRIC CO.
M-0420
5. Slowly decrease the frequency of the three-
phase test set until the relay trips. The unit
should trip at 59.50 Hz ±0.02 Hz.
6. The 81 UNDERFREQUENCY LED should
turn on and the unit should rotate displays
-TRGT- 06/22/93 10:19:12
Trip# = 14
-TRGT- 06/22/93 10:19:12
UNDERFREQUENCY #1
7. Set the frequency to 60.00 Hz.
8. Press TARGET RESET/LAMP TEST. The
81 UNDERFREQUENCY LED should turn
off. The unit should display
BECKWITH ELECTRIC CO.
M-0420
Содержание M-0420
Страница 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Страница 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Страница 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 165: ...D 1 Board Interconnections Appendix D D Board Interconnections Figure D 1 M 0420 Board Interconnections ...
Страница 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...