M-0420 Instruction Book
7–22
60 FL
V.T. FUSE-LOSS DETECTION
9. Simulate the VT fuse blown condition by
removing the voltage input from Phase A
(V
A
=0 V).
■
NOTE: In the default condition, the phase un-
dervoltage relay is blocked when the VT Fuse
Loss relay is enabled. Thus, removing the phase
voltage simulates a fuse loss without causing a
trip.
10. The unit should display
V.T. FUSE STATUS
--BLOWN--
11. The V.T. FUSE LOSS contacts should close.
The DMM should read 0.00
Ω
(closed con-
tacts).
12. Verify that the unit did not call for an under-
voltage trip.
13. Reconnect the input voltage to Phase A.
14. The V.T. FUSE LOSS contacts should open.
The DMM should read
3
Ω
(open contacts).
15. The unit should display
V.T. FUSE STATUS
--OK--
16. Check the fuse status on Phase B and Phase
C by following steps 9 through 15 above.
(Having the neutral in series with Phase C
will not affect the VT fuse-loss function.
However, the unit will trip on neutral under-
voltage when the source voltage is removed.)
—END—
1. Apply three-phase voltages as shown in Figure
7-1.
2. Set input current to 5.00 A with phase an-
gles as shown in Figure 7-2.
3. Press ENTER. The SELECT FUNCTION LED
should turn on and the unit should display
VOLTAGE RELAY
VOLT freq curr powr
C
4. Turn the knob clockwise on the unit until
the unit displays
MONITOR STATUS
B
setpts STAT config
C
5. Press ENTER. The unit should display
MONITOR VOLTAGE STATUS
VOLT freq curr powr
C
6. Turn the knob clockwise until the unit displays
MONITOR FUSE STATUS
B
FUSE temp powerup
7. Press ENTER. The SELECT FUNCTION LED
should turn off and the unit should display
V.T. FUSE STATUS
--OK--
8. Connect a digital multimeter (DMM) across
the V.T. FUSE LOSS contacts 47 and 48.
The DMM should read
3
Ω
(open contacts).
Содержание M-0420
Страница 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Страница 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Страница 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 165: ...D 1 Board Interconnections Appendix D D Board Interconnections Figure D 1 M 0420 Board Interconnections ...
Страница 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...