Test Procedures – 7
7–27
50N
INSTANTANEOUS OVERCURRENT, NEUTRAL (CONT)
Time Delay Accuracy Test
TEST SETTINGS:
Magnitude #1
9 A
Function 46
Disable
14. Rapidly increase the current on Phase C to
9.50 A. The unit should trip instantaneously
(2 cycles).
15. 50N INSTANTANEOUS OVERCURRENT
LED should turn on and the unit should rotate
displays
-TRGT- 06/22/93 10:19:12
Trip# = 17
-TRGT- 06/22/93 10:19:12
NUTRL INST. OVERCURRENT
16. Reduce the current to 0.00 A.
17. Press TARGET RESET/LAMP TEST. The
50 N INSTANTANEOUS OVERCURRENT
LED should turn off. The unit should display
BECKWITH ELECTRIC CO.
M-0420
—END—