M-0420 Instruction Book
7–2
7.3
Equipment Required
The following equipment is required to carry out
the test procedures:
1. Two Digital Multimeters (DMM) with 10 A
current range
2. 120 V ac or 0 to 125 V dc variable supply
for system power
3. Three-phase independent voltage sources
(0 to 250 V) to simulate VT inputs*
4. Three-phase variable current sources (0-25
A) to simulate CT inputs*
5. Electronic timer accurate to at least 10 ms.*
* Three Doble F2200 Test Systems or
equivalent can be used.
7.4
Test and Equipment Setup
1. Connect system power to the power input
terminals 54 (hot) and 55 (neutral). The re-
lay can be ordered with a nominal input
power supply of 120 V ac, 125 V dc, 48 V
dc, or 24 V dc.
■
NOTE: The proper power for your relay is clearly
marked on the power supply label affixed to the
rear panel.
2. Connect the voltage and current inputs ac-
cording to the configurations shown in Fig-
ures 7-1 and 7-2. Before beginning each
test, set the test voltage inputs to 120 V ac
and the current input to 2 A to simulate
normal operating conditions.
Optional
3. Ohmmeter Connection: The status of the
trip contact can be monitored by connect-
ing an ohmmeter to terminals 44 and 45.
Содержание M-0420
Страница 56: ...M 0420 Instruction Book 3 4 This Page Intentionally Left Blank ...
Страница 92: ...M 0420 Instruction Book 5 28 This Page Left Intentionally Blank ...
Страница 156: ...A 8 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 160: ...B 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 164: ...C 4 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 165: ...D 1 Board Interconnections Appendix D D Board Interconnections Figure D 1 M 0420 Board Interconnections ...
Страница 166: ...D 2 M 0420 Instruction Book This Page Intentionally Left Blank ...
Страница 174: ...E 8 M 0420 Instruction Book This Page Intentionally Left Blank ...