Commissioning/Configuration
EP3204 and EP3314
73
Version: 2.2
Index 8010: TC Settings Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
8010:15
Filter settings
Filter settings (Ch1. applies to all channels)
UINT16
RW
0x0000 (0
dec
)
0
50 Hz
1
60 Hz
2
100 Hz
3
500 Hz
4
1 kHz,
5
2 kHz
6
3.75 kHz
7
7.5 kHz
8
15 kHz
9
30 kHz
10
5 Hz
11
10 Hz
8010:16
Calibration interval
reserved
UINT16
RW
0x0000 (0
dec
)
8010:17
User calibration offset User calibration: Offset
INT16
RW
0x0000 (0
dec
)
8010:18
User calibration gain
User calibration: Gain
UINT16
RW
0x4000
(16384
dec
)
8010:19
Sensor type
Thermocouple
UINT16
RW
0x0000 (0
dec
)
0
Type K -200 °C to 1370 °C
1
Type J -100°C to 1200°C
2
Type L 0°C to 900°C
3
Type E -100°C to 1000°C
4
Type T -200°C to 400°C
5
Type N -100°C to 1300°C
6
Type U 0°C to 600°C
7
Type B 600°C to 1800°C
8
Type R 0°C to 1767°C
9
Type S 0°C to 1760°C
10
Type C 0°C to 2320°C
100 ± 30 mV (1 µV resolution)
101 ± 60 mV (2 µV resolution)
102 ± 75 mV (4 µV resolution)
8010:1B
Wire calibration 1/32
Ohm
Only for 2-wire measurements:
contains the resistance of the supply line for the tempera-
ture sensor (in 1/32 ohm).
INT16
RW
0x0000 (0
dec
)
Index 8020: TC Settings Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
8020:0
TC Settings Ch.3
Maximum subindex
UINT8
RO
0x1B (27
dec
)
8020:01
Enable user scale
Activates user scaling
BOOLEAN
RW
0x00 (0
dec
)
8020:02
Presentation
Presentation of the measured value
BIT3
RW
0x00 (0
dec
)
0
Signed, in two's complement
1
Most significant bit as sign
2
High-resolution (1/100 °C steps)
8020:05
Siemens bits
The S5 bits are displayed in the three low-order bits
BOOLEAN
RW
0x00 (0
dec
)
8020:06
Enable filter
Enable filter, which makes PLC-cycle-synchronous data
exchange unnecessary
BOOLEAN
RW
0x00 (0
dec
)
8020:07
Enable limit 1
Activates limit check for limit 1
BOOLEAN
RW
0x00 (0
dec
)
8020:08
Enable limit 2
Activates limit check for limit 2
BOOLEAN
RW
0x00 (0
dec
)
8020:0A
Enable user calibra-
tion
Activates user calibration
BOOLEAN
RW
0x00 (0
dec
)
8020:0B
Enable vendor cali-
bration
Activates vendor calibration
BOOLEAN
RW
0x01 (1
dec
)