![Beckhoff EP3204 Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/beckhoff/ep3204/ep3204_documentation_2719256060.webp)
Commissioning/Configuration
EP3204 and EP3314
60
Version: 2.2
Index 800E: RTD Internal data Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
800E:0
RTD Internal data
Ch.1
Maximum subindex
UINT8
RO
0x04 (4
dec
)
800E:01
ADC raw value 1
Raw value of the analog/digital converter
INT32
RO
0x00000000
(0
dec
)
800E:02
Resistor 1
Resistance value of the first measurement
UINT16
RO
0x0000 (0
dec
)
800E:03
ADC raw value 2
Raw value of the analog/digital converter
INT32
RO
0x00000000
(0
dec
)
800E:04
Resistor 2
Resistance value of the second measurement
UINT16
RO
0x0000 (0
dec
)
Index 800F: RTD Vendor data Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
800F:0
RTD Vendor data
Ch.1
Maximum subindex
UINT8
RO
0x07 (7
dec
)
800F:01
Calibration offset 3-
wire
Calibration for 3-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
800F:02
Calibration gain 3-
wire
Calibration for 3-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
800F:03
Calibration offset 2-
wire
Calibration for 2-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
800F:04
Calibration gain 2-
wire
Calibration for 2-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
800F:05
Calibration offset 4-
wire
Calibration for 4-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
800F:06
Calibration gain 4-
wire
Calibration for 4-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
800F:07
PGA Gain Correction Gain correction for PT1000 measurement
INT16
RW
0x0000 (0
dec
)
Index 801E: RTD Internal data Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
801E:0
RTD Internal data
Ch.2
Maximum subindex
UINT8
RO
0x04 (4
dec
)
801E:01
ADC raw value 1
Raw value of the analog/digital converter
INT32
RO
0x00000000
(0
dec
)
801E:02
Resistor 1
Resistance value of the first measurement
UINT16
RO
0x0000 (0
dec
)
801E:03
ADC raw value 2
Raw value of the analog/digital converter
INT32
RO
0x00000000
(0
dec
)
801E:04
Resistor 2
Resistance value of the second measurement
UINT16
RO
0x0000 (0
dec
)
Index 801F: RTD Vendor data Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
801F:0
RTD Vendor data
Ch.2
Maximum subindex
UINT8
RO
0x07 (7
dec
)
801F:01
Calibration offset 3-
wire
Calibration for 3-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
801F:02
Calibration gain 3-
wire
Calibration for 3-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
801F:03
Calibration offset 2-
wire
Calibration for 2-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
801F:04
Calibration gain 2-
wire
Calibration for 2-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
801F:05
Calibration offset 4-
wire
Calibration for 4-wire measurement: Offset
INT16
RW
0x0000 (0
dec
)
801F:06
Calibration gain 4-
wire
Calibration for 4-wire measurement: Gain
UINT16
RW
0x4000
(16384
dec
)
801F:07
PGA Gain Correction Gain correction for PT1000 measurement
INT16
RW
0x0000 (0
dec
)
Содержание EP3204