Index 6020: RTD Inputs Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
6020:0
RTD Inputs Ch.3
Maximum subindex
UINT8
RO
0x11 (17
dec
)
6020:01
Underrange
Is set if the value falls below the operating range of the
sensor or the process record contains the lowest possi-
ble value.
BOOLEAN
RO
0x00 (0
dec
)
6020:02
Overrange
Is set if the value exceeds the operating range of the
sensor or the process record contains the highest possi-
ble value.
BOOLEAN
RO
0x00 (0
dec
)
6020:03
Limit 1
Only when limit check is active
BIT2
RO
0x00 (0
dec
)
1
Value below set limit
2
Set limit exceeded
3
Set limit reached
6020:05
Limit 2
Only when limit check is active
BIT2
RO
0x00 (0
dec
)
1
Value below set limit
2
Set limit exceeded
3
Set limit reached
6020:07
Error
The error bit is set if the process data is invalid (cable
break, overrange, underrange)
BOOLEAN
RO
0x00 (0
dec
)
6020:0E
Sync error
Only in DC: bit is set if the slave is not able to operate
synchronous with master, because it cannot keep up with
the cycle time.
BOOLEAN
RO
0x00 (0
dec
)
6020:0F
TxPDO State
Validity of the data of the associated TxPDO
BOOLEAN
RO
0x00 (0
dec
)
0
valid
1
invalid
6020:10
TxPDO Toggle
TxPDO toggle is toggled by the slave when the data of
the associated TxPDO is updated.
BOOLEAN
RO
0x00 (0
dec
)
6020:11
Value
Analog input date
INT16
RO
0x0000 (0
dec
)
Index 6030: RTD Inputs Ch.4
Index (hex) Name
Meaning
Data type
Flags
Default
6030:0
RTD Inputs Ch.4
Maximum subindex
UINT8
RO
0x11 (17
dec
)
6030:01
Underrange
Is set if the value falls below the operating range of the
sensor or the process record contains the lowest possi-
ble value.
BOOLEAN
RO
0x00 (0
dec
)
6030:02
Overrange
Is set if the value exceeds the operating range of the
sensor or the process record contains the highest possi-
ble value.
BOOLEAN
RO
0x00 (0
dec
)
6030:03
Limit 1
Only when limit check is active
BIT2
RO
0x00 (0
dec
)
1
Value below set limit
2
Set limit exceeded
3
Set limit reached
6030:05
Limit 2
Only when limit check is active
BIT2
RO
0x00 (0
dec
)
1
Value below set limit
2
Set limit exceeded
3
Set limit reached
6030:07
Error
The error bit is set if the process data is invalid (wire
breakage, overrange, underrange).
BOOLEAN
RO
0x00 (0
dec
)
6030:0E
Sync error
Only in DC: bit is set if the slave is not able to operate
synchronous with master, because it cannot keep up with
the cycle time.
BOOLEAN
RO
0x00 (0
dec
)
6030:0F
TxPDO State
Validity of the data of the associated TxPDO
BOOLEAN
RO
0x00 (0
dec
)
0
valid
1
invalid
6030:10
TxPDO Toggle
TxPDO toggle is toggled by the slave when the data of
the associated TxPDO is updated.
BOOLEAN
RO
0x00 (0
dec
)
6030:11
Value
Analog input date
INT16
RO
0x0000 (0
dec
)