Commissioning/Configuration
EP3204 and EP3314
35
Version: 2.2
The box uses the following calculation rule:
Fig. 23: Data flow: resistance measurement with a 2 and 4-wire connection technique
With the values:
Index in the CoE directory with
n: channel number with 0 ≤ n ≤ 3 (channel 1 - 4)
X: Raw value
0x80nE:01
PT100
PT1000
2-wire
4-wire
2-wire
4-wire
Gv: Vendor Gain
0x80nF:04
0x80nF:06
0x80nF:0A
0x80nF:0C
Ov: Vendor Offset
0x80nF:03
0x80nF:05
0x80nF:09
0x80nF:0B
Y
R
: Output value in 1/256 Ω
0x80nE:02
Overflow Y
R
after 16 bits
This value is only for fault finding. The register overflows after 16 bits, i.e. at 65536.