Mounting and wiring
EL922x
53
Version: 1.0
Sample programming 2
Operation
Display
Meaning
Press button LED 1 for >3 seconds
Activate programming mode
Ready LED lights up orange
Button LED 1 flashes 6x green
Button LED 2 flashes 4x green
Programming mode is active
Output 1 is set to 6 A
Output 2 is set to 4 A
Press button LED 1 7x
Output 1 is set to 7 A
Ready LED lights up orange
Button LED 1 flashes 7x red
Button LED 2 flashes 4x red
Programming mode is active
Output 1 is set to 7 A
Output 2 is set to 4 A
Sum current of 10 A exceeded!
Press button LED2 3x
Output 2 is set to 3 A
Ready LED lights up orange
Button LED 1 flashes 7x green
Button LED 2 flashes 3x green
Programming mode is active
Output 1 is set to 7 A
Output 2 is set to 3 A
Sum current of 10 A adhered to!
Press button LED 1 for >3 seconds
Save the new settings and exit programming
mode
Sample programming 3
Operation
Display
Meaning
Press button LED 2 for >3 seconds
Activate programming mode
Ready LED lights up orange
Button LED 1 flashes 6x green
Button LED 2 flashes 4x green
Programming mode is active
Output 1 is set to 6 A
Output 2 is set to 4 A
Press button LED 1 7x
Output 1 is set to 7 A
Ready LED lights up orange
Button LED 1 flashes 7x red
Button LED 2 flashes 4x red
Programming mode is active
Output 1 is set to 7 A
Output 2 is set to 4 A
Sum current of 10 A exceeded!
Press button LED 2 11x
Output 2 is set to
Off
Ready LED lights up orange
Button LED 1 flashes 7x green
Button LED 2 is NOT lit
Programming mode is active
Output 1 is set to 7 A
Output 2 is
off
Sum current of 10 A adhered to!
Press button LED 1 for >3 seconds
Save the new settings and exit programming
mode
The EL9227-5500 / EL9222-5500 devices have a sum current limitation of 10 A
The 10 A can be split between the two channels. If one channel is set to 10 A, the other channel
must be set to OFF! If the sum current is exceeded, button LED 1 and button LED 2 flash red.
The flashing code shows how the channels have been set, and at least one channel must be
changed.
When the value falls below the maximum sum current again, button LED 1 and button LED 2 flash
green or are off. Only now can the programming mode be saved and exited.